| Plan Review Notes For Permit 22070434 |
| Permit Number |
22070434 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-11-29 06:42:27 | 2ND REVIEW FMC | | | PERMIT: 22070434 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE DRYER DUCT MATERIAL, SIZE AND | | | TERMINATION LOCATION. FRC M1502 | | | | | | 2) PROVIDE THE CFM???S OF THE KITCHEN HOOD MOTOR AS | | | MAKEUP AIR MAY BE REQUIRED. FRC M1503.4 | | | | | | 3) THE DESIGNER OF THE MECHANICAL DRAWING MUST PRINT | | | AND SIGN THEIR NAME ON THE DRAWING. FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|