| 2022-09-16 10:43:13 | PROVIDE A DETAIL OF THE DRYER DUCT AT THE RATED WALLS. | | | IF THEY PENETRATE THE RATED WALLS THEY MUST BE IN A | | | SHAFT ALL THE WAY TO THE EXTERIOR TERMINATION. FMC | | | 504.2 | | | | | | 504.2 EXHAUST PENETRATIONS. WHERE A CLOTHES DRYER | | | EXHAUST | | | DUCT PENETRATES A WALL OR CEILING MEMBRANE, THE ANNULAR | | | SPACE | | | SHALL BE SEALED WITH NONCOMBUSTIBLE MATERIAL, APPROVED | | | FIRE | | | CAULKING OR A NONCOMBUSTIBLE DRYER EXHAUST DUCT WALL | | | RECEPTACLE. | | | DUCTS THAT EXHAUST CLOTHES DRYERS SHALL NOT PENETRATE | | | OR | | | BE LOCATED WITHIN ANY FIREBLOCKING, DRAFTSTOPPING OR | | | ANY WALL, | | | FLOOR/CEILING OR OTHER ASSEMBLY REQUIRED BY THE FLORIDA | | | BUILDING | | | CODE, BUILDING TO BE FIRE-RESISTANCE RATED, UNLESS SUCH | | | DUCT IS CONSTRUCTED OF GALVANIZED STEEL OR ALUMINUM OF | | | THE | | | THICKNESS SPECIFIED IN SECTION 603.4 AND THE | | | FIRE-RESISTANCE | | | RATING IS MAINTAINED IN ACCORDANCE WITH THE FLORIDA | | | BUILDING | | | CODE, BUILDING. FIRE DAMPERS, COMBINATION FIRE/SMOKE | | | DAMPERS | | | AND ANY SIMILAR DEVICES THAT WILL OBSTRUCT THE EXHAUST | | | FLOW | | | SHALL BE PROHIBITED IN CLOTHES DRYER EXHAUST DUCTS. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|