Plan Review Notes
Plan Review Notes For Permit 22070389
Permit Number 22070389
Review Stop P
Sequence Number 2
Notes
Date Text
2022-09-16 16:29:532ND REVIEW FBC-2020 PLUMBING
 PERMIT-22070389
 8/2/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES
  
 1) FAILED. SHEETS P2.1 & P5.1: THE DRAINAGE FROM HAND
 SINKS- 21 & 50 SHALL DISCHARGE INTO THE SANITARY SYSTEM
 AND NOT THE GREASE WASTE AS SHOWN ON THE PLANS- SEC.
 1003.3.1 FBC P. PLEASE CORRECT THE DRAWINGS.
  
 THE SANITARY RISER SHOWS HANDSINK- 50 DRAINING INTO THE
 GREASE WASTE.
  
 2) FAILED. P2.1 & P5.1: THE DRAINAGE FROM THE MOP SINK,
 THE FLOOR DRAINS IN THE WALK-IN COOLER, AND THE FLOOR
 DRAINS AT THE UNDER BAR DUMP SINK (B.1) & THE
 WAREWASHER (B.3) SHALL DISCHARGE INTO THE GREASE WASTE
 LINE AND NOT THE SANITARY AS SHOWN ON THE PLANS- SEC.
 1003.3.1 FBC P- PLEASE CORRECT THE DRAWINGS. PLEASE
 NOTE THE LOCATION OF B.1 IS NOT SHOWN ON THE SANITARY
 AND WATER RISERS, AND THE SANITARY RISER SHOWS THE
 DRAINAGE FROM THE CORNER SINK (30) DISCHARGING FROM THE
 FLOOR DRAIN INTO THE SANITARY LINE.
  
 THE REVISED P.2.1 SHOWS DRAINAGE FROM THE ICE CHESTS
 (B.5 & B.8) AND ICE MAKERS(B.11 & B.12) DISCHARGING
 INTO THE GREASE WASTE LINE INSTEAD OF THE SANTARY- SEC.
 1003.3.1 FBC P.
 NO CORRECTIONS WERE MADE TO THE SANITARY RISER ON P.5.1
 WITH THE EXCEPTION OF THE DRAINAGE FROM HANDSINK-21 WAS
 RELOCATED TO THE SANITARY. PLEASSE MATCH THE RISER WITH
 THE PIPING LAYOUT PLAN.
  
  
 4) FAILED. P5.1 PLEASE PLACE A NOTE ON THE PLAN
 INDICATING THE GREASE INTERCEPTOR SHALL BE INSTALLED
 UNDER A SEPARATE PERMIT- SEC. 105.1 WPB. PLEASE NOTE
 THE FOLLOWING: DUE TO A CHANGE IN PROCESS, THE GREASE
 INTERCEPTOR PERMIT IS REQUIRED TO BE SUBMITTED PRIOR TO
 ISSUANCE OF THE PRIMARY PERMIT. YOU CAN SUBMIT AN
 APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL
 AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER