| Date |
Text |
| 2022-09-16 16:29:53 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT-22070389 |
| | 8/2/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES |
| | |
| | 1) FAILED. SHEETS P2.1 & P5.1: THE DRAINAGE FROM HAND |
| | SINKS- 21 & 50 SHALL DISCHARGE INTO THE SANITARY SYSTEM |
| | AND NOT THE GREASE WASTE AS SHOWN ON THE PLANS- SEC. |
| | 1003.3.1 FBC P. PLEASE CORRECT THE DRAWINGS. |
| | |
| | THE SANITARY RISER SHOWS HANDSINK- 50 DRAINING INTO THE |
| | GREASE WASTE. |
| | |
| | 2) FAILED. P2.1 & P5.1: THE DRAINAGE FROM THE MOP SINK, |
| | THE FLOOR DRAINS IN THE WALK-IN COOLER, AND THE FLOOR |
| | DRAINS AT THE UNDER BAR DUMP SINK (B.1) & THE |
| | WAREWASHER (B.3) SHALL DISCHARGE INTO THE GREASE WASTE |
| | LINE AND NOT THE SANITARY AS SHOWN ON THE PLANS- SEC. |
| | 1003.3.1 FBC P- PLEASE CORRECT THE DRAWINGS. PLEASE |
| | NOTE THE LOCATION OF B.1 IS NOT SHOWN ON THE SANITARY |
| | AND WATER RISERS, AND THE SANITARY RISER SHOWS THE |
| | DRAINAGE FROM THE CORNER SINK (30) DISCHARGING FROM THE |
| | FLOOR DRAIN INTO THE SANITARY LINE. |
| | |
| | THE REVISED P.2.1 SHOWS DRAINAGE FROM THE ICE CHESTS |
| | (B.5 & B.8) AND ICE MAKERS(B.11 & B.12) DISCHARGING |
| | INTO THE GREASE WASTE LINE INSTEAD OF THE SANTARY- SEC. |
| | 1003.3.1 FBC P. |
| | NO CORRECTIONS WERE MADE TO THE SANITARY RISER ON P.5.1 |
| | WITH THE EXCEPTION OF THE DRAINAGE FROM HANDSINK-21 WAS |
| | RELOCATED TO THE SANITARY. PLEASSE MATCH THE RISER WITH |
| | THE PIPING LAYOUT PLAN. |
| | |
| | |
| | 4) FAILED. P5.1 PLEASE PLACE A NOTE ON THE PLAN |
| | INDICATING THE GREASE INTERCEPTOR SHALL BE INSTALLED |
| | UNDER A SEPARATE PERMIT- SEC. 105.1 WPB. PLEASE NOTE |
| | THE FOLLOWING: DUE TO A CHANGE IN PROCESS, THE GREASE |
| | INTERCEPTOR PERMIT IS REQUIRED TO BE SUBMITTED PRIOR TO |
| | ISSUANCE OF THE PRIMARY PERMIT. YOU CAN SUBMIT AN |
| | APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE |
| | A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT |
| | APPLICATION TO [email protected] . YOU WILL |
| | RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| | MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| | APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT |
| | YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER |
| | YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL |
| | AND I WILL CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |