Plan Review Notes
Plan Review Notes For Permit 22070389
Permit Number 22070389
Review Stop P
Sequence Number 1
Notes
Date Text
2022-08-03 07:51:221ST REVIEW FBC-2020 PLUMBING
 PERMIT-22070389
 8/2/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P2.1 & P5.1: THE DRAINAGE FROM HAND SINKS 21
 & 50 SHALL DISCHARGE INTO THE SANITARY SYSTEM AND NOT
 THE GREASE WASTE AS SHOWN ON THE PLANS- SEC. 1003.3.1
 FBC P. PLEASE CORRECT THE DRAWINGS.
  
 2) P2.1 & P5.1: THE DRAINAGE FROM THE MOP SINK, THE
 FLOOR DRAINS IN THE WALK-IN COOLER, AND THE FLOOR
 DRAINS AT THE UNDER BAR DUMP SINK (B.1) & THE
 WAREWASHER (B.3) SHALL DISCHARGE INTO THE GREASE WASTE
 LINE AND NOT THE SANITARY AS SHOWN ON THE PLANS- SEC.
 1003.3.1 FBC P- PLEASE CORRECT THE DRAWINGS. PLEASE
 NOTE THE LOCATION OF B.1 IS NOT SHOWN ON THE SANITARY
 AND WATER RISERS, AND THE SANITARY RISER SHOWS THE
 DRAINAGE FROM THE CORNER SINK (30) DISCHARGING FROM THE
 FLOOR DRAIN INTO THE SANITARY LINE.
  
 3) P5.1: SPECS AND CALCULATIONS HAVE BEEN PROVIDED FOR
 A SCHIER GB-250 GREASE INTERCEPTOR HOWEVER A SCHIER
 SI-50 SOLIDS INTERCEPTOR IS SHOWN ON THE RISER DRAWING-
 PLEASE CORRECT- SEC. 107.2.1 WPB.
  
 4) P5.1 PLEASE PLACE A NOTE ON THE PLAN INDICATING THE
 GREASE INTERCEPTOR SHALL BE INSTALLED UNDER A SEPARATE
 PERMIT- SEC. 105.1 WPB. PLEASE NOTE THE FOLLOWING: DUE
 TO A CHANGE IN PROCESS, THE GREASE INTERCEPTOR PERMIT
 IS REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE
 PRIMARY PERMIT. YOU CAN SUBMIT AN APPLICATION "TBD" (TO
 BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED
 BY EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL
 CHANGE THE REVIEW STATUS TO PASS.
 5) P3.1 & P5.1: SHOW THE MEANS OF PROVIDING TEMPERED
 WATER DELIVERY FROM THE LAVATORIES- SECS. 419.5 &
 607.1.2 FBC P.
  
 6) P3.1 & P5.1: PROVIDE A MEANS OF LIMITING THE HOT
 WATER TEMPERATURE AT THE MOP SINK, WAREWASHERS, PREP
 SINKS ETC.- SEC. 607.1.1 FBC P. BECAUSE THE THERMOSTAT
 ON THE WATER HEATER CANNOT BE THE MEANS OF LIMITING THE
 TEMPERATURE, TYPICALLY A MASTER THERMOSTATIC MIXING
 VALVE OR POINT OF USE MIXING VALVES ARE INSTALLED.
  
 7) A9.0.1 DETAIL A: PROVIDE THE LENGTH AND WIDTH
 DIMENSIONS OF THE RESTROOMS- SEC. 107.2.1 WPB.
  
 8) A9.0.1 DETAIL A: SHOW THE DIMENSIONS OF THE CLEAR
 FLOOR SPACES FOR THE WATER CLOSETS AND LAVATORIES-
 SECS. 604.3 & 606.2 FBC ACC.
  
 9) A9.0.1 DETAILS 1 & 6: SHOW THE HEIGHT MEASUREMENTS
 OF THE GRAB BARS MEASURED FROM THE FINISHED FLOORS TO
 THE TOPS OF THE GRAB BARS- SEC. 609.4 FBC ACC.
  
 10) A9.0.1 DETAILS 1 & 6: SHOW THE HEIGHT MEASUREMENTS
 OF THE MIRRORS MEASURED FROM THE FINISHED FLOORS TO THE
 BOTTOMS OF THE REFLECTIVE SURFACES- SEC. 603.3 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  