| 2022-08-03 07:51:22 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT-22070389 |
| | 8/2/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P2.1 & P5.1: THE DRAINAGE FROM HAND SINKS 21 |
| | & 50 SHALL DISCHARGE INTO THE SANITARY SYSTEM AND NOT |
| | THE GREASE WASTE AS SHOWN ON THE PLANS- SEC. 1003.3.1 |
| | FBC P. PLEASE CORRECT THE DRAWINGS. |
| | |
| | 2) P2.1 & P5.1: THE DRAINAGE FROM THE MOP SINK, THE |
| | FLOOR DRAINS IN THE WALK-IN COOLER, AND THE FLOOR |
| | DRAINS AT THE UNDER BAR DUMP SINK (B.1) & THE |
| | WAREWASHER (B.3) SHALL DISCHARGE INTO THE GREASE WASTE |
| | LINE AND NOT THE SANITARY AS SHOWN ON THE PLANS- SEC. |
| | 1003.3.1 FBC P- PLEASE CORRECT THE DRAWINGS. PLEASE |
| | NOTE THE LOCATION OF B.1 IS NOT SHOWN ON THE SANITARY |
| | AND WATER RISERS, AND THE SANITARY RISER SHOWS THE |
| | DRAINAGE FROM THE CORNER SINK (30) DISCHARGING FROM THE |
| | FLOOR DRAIN INTO THE SANITARY LINE. |
| | |
| | 3) P5.1: SPECS AND CALCULATIONS HAVE BEEN PROVIDED FOR |
| | A SCHIER GB-250 GREASE INTERCEPTOR HOWEVER A SCHIER |
| | SI-50 SOLIDS INTERCEPTOR IS SHOWN ON THE RISER DRAWING- |
| | PLEASE CORRECT- SEC. 107.2.1 WPB. |
| | |
| | 4) P5.1 PLEASE PLACE A NOTE ON THE PLAN INDICATING THE |
| | GREASE INTERCEPTOR SHALL BE INSTALLED UNDER A SEPARATE |
| | PERMIT- SEC. 105.1 WPB. PLEASE NOTE THE FOLLOWING: DUE |
| | TO A CHANGE IN PROCESS, THE GREASE INTERCEPTOR PERMIT |
| | IS REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE |
| | PRIMARY PERMIT. YOU CAN SUBMIT AN APPLICATION "TBD" (TO |
| | BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED |
| | BY EMAILING A COMPLETED PERMIT APPLICATION TO |
| | [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE |
| | PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL |
| | CHANGE THE REVIEW STATUS TO PASS. |
| | 5) P3.1 & P5.1: SHOW THE MEANS OF PROVIDING TEMPERED |
| | WATER DELIVERY FROM THE LAVATORIES- SECS. 419.5 & |
| | 607.1.2 FBC P. |
| | |
| | 6) P3.1 & P5.1: PROVIDE A MEANS OF LIMITING THE HOT |
| | WATER TEMPERATURE AT THE MOP SINK, WAREWASHERS, PREP |
| | SINKS ETC.- SEC. 607.1.1 FBC P. BECAUSE THE THERMOSTAT |
| | ON THE WATER HEATER CANNOT BE THE MEANS OF LIMITING THE |
| | TEMPERATURE, TYPICALLY A MASTER THERMOSTATIC MIXING |
| | VALVE OR POINT OF USE MIXING VALVES ARE INSTALLED. |
| | |
| | 7) A9.0.1 DETAIL A: PROVIDE THE LENGTH AND WIDTH |
| | DIMENSIONS OF THE RESTROOMS- SEC. 107.2.1 WPB. |
| | |
| | 8) A9.0.1 DETAIL A: SHOW THE DIMENSIONS OF THE CLEAR |
| | FLOOR SPACES FOR THE WATER CLOSETS AND LAVATORIES- |
| | SECS. 604.3 & 606.2 FBC ACC. |
| | |
| | 9) A9.0.1 DETAILS 1 & 6: SHOW THE HEIGHT MEASUREMENTS |
| | OF THE GRAB BARS MEASURED FROM THE FINISHED FLOORS TO |
| | THE TOPS OF THE GRAB BARS- SEC. 609.4 FBC ACC. |
| | |
| | 10) A9.0.1 DETAILS 1 & 6: SHOW THE HEIGHT MEASUREMENTS |
| | OF THE MIRRORS MEASURED FROM THE FINISHED FLOORS TO THE |
| | BOTTOMS OF THE REFLECTIVE SURFACES- SEC. 603.3 FBC ACC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |