Plan Review Notes
Plan Review Notes For Permit 22070389
Permit Number 22070389
Review Stop G
Sequence Number 1
Notes
Date Text
2022-08-03 08:26:591ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22070389
 8/3/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P5.1 GAS PIPING ISOMETRIC CORRECTIONS:
 A) THE 1-1/4-INCH MAIN SUPPLY PIPE FROM THE METER
 REGULATOR TO THE TEE IS UNDERSIZED PER THE SIZING TABLE
 402.4(2) FBC FG THAT IS LISTED ON THE PLAN. BASED ON
 THE 1,512,000 BTU LOAD AT 42 FT. TDL A MINIMUM 2-INCH
 SUPPLY PIPE IS REQUIRED.
 B) PER TABLE 402.4(2), THE 3/4-INCH PIPES SUPPLYING THE
 495,000 BTU OVEN/STEAMERS SHALL BE INCREASED IN SIZE TO
 1-1/4 INCH.
  
 2) P5.1: PLEASE CORRECT THE COMBUSTION AIR CALCULATIONS
 TO SHOW THE KITCHEN APPLIANCE LOAD AT 1,313,000 BTUS,
 AND 460 CFMS OF AIR REQUIRED. PLEASE NOTE THAT HOOD
 MAKEUP IS DEDICATED REPLACEMENT AIR FOR HOOD EXHAUST
 AND CANNOT BE THE SOURCE OF COMBUSTION AIR FOR THE
 APPLIANCES- SEE SEC. 304.9.3 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  