| Plan Review Notes For Permit 22070389 |
| Permit Number |
22070389 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-08-03 08:26:59 | 1ST REVIEW FBC-2020 FUEL GAS | | | PERMIT- 22070389 | | | 8/3/2022 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P5.1 GAS PIPING ISOMETRIC CORRECTIONS: | | | A) THE 1-1/4-INCH MAIN SUPPLY PIPE FROM THE METER | | | REGULATOR TO THE TEE IS UNDERSIZED PER THE SIZING TABLE | | | 402.4(2) FBC FG THAT IS LISTED ON THE PLAN. BASED ON | | | THE 1,512,000 BTU LOAD AT 42 FT. TDL A MINIMUM 2-INCH | | | SUPPLY PIPE IS REQUIRED. | | | B) PER TABLE 402.4(2), THE 3/4-INCH PIPES SUPPLYING THE | | | 495,000 BTU OVEN/STEAMERS SHALL BE INCREASED IN SIZE TO | | | 1-1/4 INCH. | | | | | | 2) P5.1: PLEASE CORRECT THE COMBUSTION AIR CALCULATIONS | | | TO SHOW THE KITCHEN APPLIANCE LOAD AT 1,313,000 BTUS, | | | AND 460 CFMS OF AIR REQUIRED. PLEASE NOTE THAT HOOD | | | MAKEUP IS DEDICATED REPLACEMENT AIR FOR HOOD EXHAUST | | | AND CANNOT BE THE SOURCE OF COMBUSTION AIR FOR THE | | | APPLIANCES- SEE SEC. 304.9.3 FBC FG. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|