Plan Review Notes
Plan Review Notes For Permit 22070299
Permit Number 22070299
Review Stop B
Sequence Number 2
Notes
Date Text
2022-08-29 13:18:11JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R36
 COVERS MULTIPLE ATTACHMENT LIMITATIONS. SELECT
 ATTACHMENT LIMITATION SYSTEM USED FROM 5.8.3.2
 MECHANICALLY ATTACHED BASE SHEET PAGES #8-16. SELECTED
 SYSTEM MUST MEET OR EXCEED THE MINIMUM DESIGN PRESSURE
 REQUIREMENTS FOR A HIP ROOF; 6/12 ROOF SLOPE; MEAN ROOF
 HEIGHT 25 FT. MINIMUM DESIGN PRESSURE REQUIREMENT OF
 -78 AS PER CHAPTER 3 OF THE 2020 FBC RESIDENTIAL.
 SELECT SYSTEM THAT MEETS OR EXCEEDS THIS REQUIREMENT.
 ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  