| 2022-09-02 10:38:31 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22070296 |
| | 9/2/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET EP-1: PROVIDE A WATER RISER DRAWING FOR THE |
| | RELOCATED EYE WASH STATION- SEC. 107.3.5.1.3 WPB AND |
| | SEC. 411.3 FBC P. PLEASE IF HOT WATER IS SUPPLIED TO |
| | THE FIXTURE, THE TEMPERATURE OF THE WATER SHALL BE |
| | CONTROLLED BY A TEMPERATURE ACTUATED MIXING VALVE |
| | COMPLYING WITH ASSE 1071. |
| | |
| | 2) EP-1: PLACE A NOTE INDICATING THE EYEWASH STATION |
| | CONFORMS TO ISEA Z358.1- SEC. 411.1 FBC P. IF THE |
| | RELOCATED STATION DOES NOT CONFORM, THEN IT SHALL BE |
| | REPLACED WITH A NEW CONFORMING MODEL. |
| | |
| | 3) EP-1: PROVIDE A LEGEND ON THE PLAN THAT CORRESPONDS |
| | WITH THE NUMBERED NOTES IN THE NEW POOL EQUIPMENT AREA- |
| | SEC.107.2.1 WPB. PLEASE IDENTIFY THE MAKES AND MODELS |
| | OF THE EQUIPMENT TO MATCH WITH THE EQUIPMENT SHOWN IN |
| | THE SCHEMATIC DRAWING. |
| | |
| | 4) EP-1: THE PLAN HAS A POOL PIPING SCHEMATIC AND A |
| | POOL PIPING DIAGRAM THAT DO NOT MATCH- SEC. 107.2.1 |
| | WPB. |
| | A) THE SCHEMATIC INCLUDES SPA PIPING THAT IS PROPOSED |
| | TO BE REMOVED. |
| | B) THE SCHEMATIC SHOWS A 2.7 HP PUMP WHICH DOES NOT |
| | MATCH WITH THE 2HP-PUMP IN THE DIAGRAM. |
| | C) THE SCHEMATIC PROVIDES PIPE SIZES, THE DIAGRAM DOES |
| | NOT PROVIDE PIPE SIZES. |
| | |
| | 4) EP-1: THE PLUMBING PLAN INDICATES ALL POOL PIPING TO |
| | BE 2-INCHES IN DIAMETER WHICH DOES NOT MATCH THE PIPE |
| | SIZES IN THE SCHEMATIC- SEC. 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |