| 2022-07-29 11:28:04 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22070296 |
| | 7/29/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS D-1 & A-1: SHOW THE NEW ACCESSIBLE POOL |
| | BATHROOM LOCATIONS AND PROVIDE COMPLETE PLUMBING PLANS |
| | PER SEC.107.3.5.1.3 WPB. PLEASE INCLUDE: |
| | A) PLUMBING RISER DRAWINGS. |
| | B) PLUMBING PIPING FLOOR PLAN DRAWINGS. |
| | C) ACCESSIBLE PLUMBING FIXTURE AND ACCESSORY |
| | INSTALLATION DRAWINGS INCLUDING FLOOR PLANS AND |
| | ELEVATION DETAILS. |
| | |
| | NOTE: THE POOL BATHROOM DESIGN AND CONSTRUCTION SHALL |
| | BE IN COMPLIANCE WITH SECS. 403.6- 403.6.3 FBC P, AND |
| | SEC. 454.1.6.1- 454.1.6.1.1- 454.1.6.1.4 INCLUDING |
| | INSTALLATION OF DIAPER CHANGING STATIONS IN EACH |
| | BATHROOM, AND INSTALLATION OF A HOSE BIB WITH VACUUM |
| | BREAKER WITHIN 25 FT. OF THE BATHROOMS. |
| | |
| | 2) A-1: REMOVE THE SPA PUMP EQUIPMENT AREA- THE SPA IS |
| | BEING DEMOLISHED- SEC. 107.2.1 WPB. |
| | |
| | 3) A-1: INDICATE THE TYPE OF BACKFLOW PREVENTER TO BE |
| | INSTALLED AND THE PURPOSE OF THE DEVICE. IS THERE AN |
| | EXISTING AUTO FILL OR NEW TO BE INSTALLED- PLEASE |
| | CLARIFY. PROVIDE A NOTE INDICATING THAT THE |
| | INSTALLATION SHALL BE COMPLETED UNDER A SEPARATE |
| | PERMIT- SECS. 608.3 & 608.17.4.1 FBC P, AND SECS. 105.1 |
| | & 107.2.1 WPB. |
| | |
| | 4) A-1: A HOSE BIB WITH VACUUM BREAKER IS REQUIRED IN |
| | THE NEW EQUIPMENT AREA- 454.1.5.9 FBC B. SHOW THE |
| | LOCATION AND ADD IT TO THE KEY NOTES. |
| | |
| | 5) A-1: SHOW THE LOCATION OF THE EXISTING OR NEW RINSE |
| | SHOWER- SEC. 454.1.6.2 FFBC B. |
| | |
| | 6) A-1: PROVIDE A WATER RISER DRAWING SHOWING THE |
| | POTABLE WATER PIPING DISTRIBUTION LINES ASSOCIATED WITH |
| | THE NEW POOL EQUIPMENT AREA- SEC. 107.3.5.1.3 WPB. |
| | |
| | 7) A-1: IN ORDER TO CLARIFY THE SCOPE OF WORK FOR THE |
| | POOL RECIRCULATION LINES PLEASE MODIFY THE NEW WATER |
| | LINES NOTE ON THE PLAN. IS THIS THE POINT OF CONNECTION |
| | FOR NEW LINES TO CONNECT TO THE EXISTING, OR ARE NEW |
| | LINES TO BE INSTALLED IN ENTIRETY FROM THE EQUIPMENT |
| | AREA TO THE POOL? -SEC. 107.2.1 WPB. A) PLEASE INDICATE |
| | THE TYPES AND SIZES OF PIPES SHOWN ON THE DRAWING. |
| | |
| | 8) A-1: PROVIDE AN ENLARGED PIPING DIAGRAM FOR THE POOL |
| | RECIRCULATION SYSTEM SHOWING THE NEW SUCTION AND |
| | PRESSURE PIPING RUNS, PIPE SIZES AND VELOCITIES- SEE |
| | SEC. 454.1.6.5.8 FBC B. |
| | |
| | 9) A-1: BECAUSE THE PUMP HAS BEEN RELOCATED IT'S |
| | IMPORTANT TO VERIFY POOL TURNOVER RATE WILL BE |
| | MAINTAINED- 4 HOURS FOR POOLS OVER 1000 FT., AND |
| | 8-HOURS FOR POOLS UNDER 1000 FT.- SEC. 454.1.6.5.2 FBC |
| | B. THE RELOCATED PUMP SHALL PROVIDE THE REQUIRED FLOW |
| | RATE AGAINST A TOTAL DYNAMIC HEAD OF 60 FT. PLEASE |
| | PROVIDE TDH CALCULATIONS, GPM FLOW RATE AND POOL |
| | TURNOVER RATE- SEC. 454.1.6.5.4 FBC B. PLEASE INCLUDE |
| | THE MAKE AND MODEL OF THE PUMP AND PUMP CURVE. |
| | |
| | 10) A-1: INDICATE ELECTRIC OR GAS POOL HEATER IN THE |
| | NOTES, AND NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR |
| | GAS PIPING- SEC. 105.1 7 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |