Plan Review Notes
Plan Review Notes For Permit 22070296
Permit Number 22070296
Review Stop P
Sequence Number 1
Notes
Date Text
2022-07-29 11:28:041ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22070296
 7/29/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS D-1 & A-1: SHOW THE NEW ACCESSIBLE POOL
 BATHROOM LOCATIONS AND PROVIDE COMPLETE PLUMBING PLANS
 PER SEC.107.3.5.1.3 WPB. PLEASE INCLUDE:
 A) PLUMBING RISER DRAWINGS.
 B) PLUMBING PIPING FLOOR PLAN DRAWINGS.
 C) ACCESSIBLE PLUMBING FIXTURE AND ACCESSORY
 INSTALLATION DRAWINGS INCLUDING FLOOR PLANS AND
 ELEVATION DETAILS.
  
 NOTE: THE POOL BATHROOM DESIGN AND CONSTRUCTION SHALL
 BE IN COMPLIANCE WITH SECS. 403.6- 403.6.3 FBC P, AND
 SEC. 454.1.6.1- 454.1.6.1.1- 454.1.6.1.4 INCLUDING
 INSTALLATION OF DIAPER CHANGING STATIONS IN EACH
 BATHROOM, AND INSTALLATION OF A HOSE BIB WITH VACUUM
 BREAKER WITHIN 25 FT. OF THE BATHROOMS.
  
 2) A-1: REMOVE THE SPA PUMP EQUIPMENT AREA- THE SPA IS
 BEING DEMOLISHED- SEC. 107.2.1 WPB.
  
 3) A-1: INDICATE THE TYPE OF BACKFLOW PREVENTER TO BE
 INSTALLED AND THE PURPOSE OF THE DEVICE. IS THERE AN
 EXISTING AUTO FILL OR NEW TO BE INSTALLED- PLEASE
 CLARIFY. PROVIDE A NOTE INDICATING THAT THE
 INSTALLATION SHALL BE COMPLETED UNDER A SEPARATE
 PERMIT- SECS. 608.3 & 608.17.4.1 FBC P, AND SECS. 105.1
 & 107.2.1 WPB.
  
 4) A-1: A HOSE BIB WITH VACUUM BREAKER IS REQUIRED IN
 THE NEW EQUIPMENT AREA- 454.1.5.9 FBC B. SHOW THE
 LOCATION AND ADD IT TO THE KEY NOTES.
  
 5) A-1: SHOW THE LOCATION OF THE EXISTING OR NEW RINSE
 SHOWER- SEC. 454.1.6.2 FFBC B.
  
 6) A-1: PROVIDE A WATER RISER DRAWING SHOWING THE
 POTABLE WATER PIPING DISTRIBUTION LINES ASSOCIATED WITH
 THE NEW POOL EQUIPMENT AREA- SEC. 107.3.5.1.3 WPB.
  
 7) A-1: IN ORDER TO CLARIFY THE SCOPE OF WORK FOR THE
 POOL RECIRCULATION LINES PLEASE MODIFY THE NEW WATER
 LINES NOTE ON THE PLAN. IS THIS THE POINT OF CONNECTION
 FOR NEW LINES TO CONNECT TO THE EXISTING, OR ARE NEW
 LINES TO BE INSTALLED IN ENTIRETY FROM THE EQUIPMENT
 AREA TO THE POOL? -SEC. 107.2.1 WPB. A) PLEASE INDICATE
 THE TYPES AND SIZES OF PIPES SHOWN ON THE DRAWING.
  
 8) A-1: PROVIDE AN ENLARGED PIPING DIAGRAM FOR THE POOL
 RECIRCULATION SYSTEM SHOWING THE NEW SUCTION AND
 PRESSURE PIPING RUNS, PIPE SIZES AND VELOCITIES- SEE
 SEC. 454.1.6.5.8 FBC B.
  
 9) A-1: BECAUSE THE PUMP HAS BEEN RELOCATED IT'S
 IMPORTANT TO VERIFY POOL TURNOVER RATE WILL BE
 MAINTAINED- 4 HOURS FOR POOLS OVER 1000 FT., AND
 8-HOURS FOR POOLS UNDER 1000 FT.- SEC. 454.1.6.5.2 FBC
 B. THE RELOCATED PUMP SHALL PROVIDE THE REQUIRED FLOW
 RATE AGAINST A TOTAL DYNAMIC HEAD OF 60 FT. PLEASE
 PROVIDE TDH CALCULATIONS, GPM FLOW RATE AND POOL
 TURNOVER RATE- SEC. 454.1.6.5.4 FBC B. PLEASE INCLUDE
 THE MAKE AND MODEL OF THE PUMP AND PUMP CURVE.
  
 10) A-1: INDICATE ELECTRIC OR GAS POOL HEATER IN THE
 NOTES, AND NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR
 GAS PIPING- SEC. 105.1 7 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  