| 2022-09-14 09:36:06 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE SIGNED AND SEALED PRE-FAB GENERATOR PAD | | | ENGINEERING THAT WAS SUBMITTED IS NOT THE ONE FOR THE | | | GENERATOR SPECIFICATIONS THAT WAS SUBMITTED. THE PAD | | | REQUIRES A MINIMUM WEIGHT OF 747 LBS. AND THE SPECS. | | | LIST THE WEIGHT OF THE GENERATOR AS 466 LBS. SUBMIT THE | | | CORRECT PAD ENGINEERING. FBC 107.2.1 |
|