Plan Review Notes
Plan Review Notes For Permit 22070234
Permit Number 22070234
Review Stop M
Sequence Number 2
Notes
Date Text
2022-09-14 13:31:15PLEASE SEE PREVIOUS REVIEW COMMENT.
  
 PROVIDE THE OUTDOOR AIR CALCULATIONS BASED OFF OF TABLE
 403.3.1.1 AND NOT THE ARCHITECTUAL LAYOUT. FMC
 403.3.1.1
  
 THE OCCUPANT LOAD UTILIZED FOR DESIGN OF THE
 VENTILATION SYSTEM SHALL BE NOT LESS THAN THE NUMBER
 DETERMINED FROM THE ESTIMATED MAXIMUM OCCUPANT LOAD
 RATE INDICATED IN TABLE 403.3.1.1.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  