| 2022-07-20 09:15:07 | 1ST PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2020 FPC - 607.1.1 - PLEASE DETAIL THE LIMIT FOR | | | "HOT WATER" DELIVERY. I SEE YOUR NOTE FOR THE LIMITING | | | OF TEMPERED WATER BY A DEVICE CONFORMING TO ASSE 1070. | | | THIS REQUIREMENT IS IN ADDITION TO 607.1.2/419.5, AND | | | REQUIRES THAT THE "THERMOSTAT FOR THE WATER SHALL NOT | | | SERVE AS THE LIMITING MEANS" FOR HOT WATER DELIVERY. | | | THIS SHOULD BE DETAILED IN YOUR WATER HEATER DETAIL OR | | | AT EACH FIXTURE THAT REQUIRES HOT WATER. | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|