Plan Review Notes
Plan Review Notes For Permit 22070234
Permit Number 22070234
Review Stop B
Sequence Number 1
Notes
Date Text
2022-08-09 13:45:45WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22070234
 ADD: 721 VILLAGE BLVD. # 107A
 CONT: URBAN ENTERPRISE CONSTRUCTION LLC
 TEL: 561-771-0047
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. AUGUST 09TH/2022
 ACTION: DENIED
  
 1) COVERSHEET:
 1A) PROJECT DIRECTORY GOVERNING AGENCIES LIST CITY OF
 WEST PALM BEACH BUT PALM BEACH COUNTY ADDRESS AND PHONE
 NUMBER NOT THE CITY. PLEASE CORRECT.
  
 1B) BUILDING DESCRIPTION LIST THE CURRENT OCCUPANCY AS
 BUSINESS AND THE PROPOSED OCCUPANCY (NOTE 5.0) TYPE AS
 BUSINESS. PLEASE REFER TO THE 2020 FBC-BUILDING SECTION
 303.4 A-3 ASSEMBLY OCCUPANCIES GYMNASIUMS WITHOUT
 SPECTATOR SEATING. PLEASE UPDATE PLAN.
  
 1C) (NOTE 6) REQUIRED OCCUPANCY SEPARATION INDICATED 1
 HOUR. (NOTE 11) NO SPRINKLERS. PLEASE REVIEW IN THE
 2020 FBC-BUILDING CODE TABLE 508.4, REQUIRES A 2-HOUR
 OCCUPANCY FIRE RATING BETWEEN A3 & B OCCUPANCIES,
 PLEASE CORRECT AND GIVE UL WALL DETAIL FOR A 2-HOUR
 FIRE RATED WALL. TABLE 508.4 & SECTION 707.3.9 SEPARATE
 OCCUPANCIES.
  
 1D) EGRESS REQUIREMENTS STATES COMMON PATH OF TRAVEL
 SECTION 1029.8 > 50 MAXIMUM TRAVEL 30 FEET. THIS
 SECTION OF CODE AND SURROUNDING CODE SECTIONS ARE
 TALKING ABOUT STADIUM/ THEATER TYPE SEATING. PLEASE
 REFER TO TABLE 1006.2.1 ASSEMBLY OCCUPANT LOAD > 30
 NON-SPRINKLERED TRAVEL DISTANCE 75 FEET. REQUIRES 2
 EXITS.
  
 1E) CLASSIFICATION OF WORK PLEASE REVIEW 2020 EXIST.
 BUILD. CODE SECTION 506.2 CHANGE IN OCCUPANCY
 APPLICATION & SECTION 1001.2.2.1 PARTIAL CHANGE OF
 OCCUPANCY, SECTION 1012 SHALL APPLY.
  
 2) SHEET CS-3:
 2A) ACCESSIBILITY PLAN SHOW COMPLIANCE WITH 1004.1
 EXERCISE MACHINES AND EQUIPMENT. CLEAR FLOOR SPACE.
  
 2B) LOBBY RECEPTIONIST DESK DOES NOT SHOW ELEVATION
 VIEWS OF THE DESK 902.1. WORK SURFACES SHALL COMPLY
 WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. EXAMPLES
 OF WORK SURFACES INCLUDE WRITING SURFACES, STUDY
 CARRELS, STUDENT LABORATORY STATIONS, BABY CHANGING AND
 OTHER TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ADA SCOPING
 PROVISIONS, EMPLOYEE WORKSTATIONS.
  
 2)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2)(2) 902.3 HEIGHT. THE TOPS OF WORK SURFACES SHALL BE
 28 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 3) SHEET A-1 WALL TYPES SCHEDULE DOES NOT SHOW THE
 MEN?S RESTROOM IN SCHEDULE AND NEITHER THE WOMEN?S
 RESTROOM NOR UTILITY ROOM (MOP SINK) SHEET CS2 NEITHER
 SHOWS COMPLIANCE WITH:
 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT
 IS A RESULT OF THE BUILDING OFFICIAL INTERPRETATION ON
 06/2020. IN BATHROOMS, RESTROOMS & SERVICE SINK AREAS
 EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH HARD,
 NON-ABSORBENT SURFACE.
  
 3A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 3B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER