| Plan Review Notes For Permit 22070231 |
| Permit Number |
22070231 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-08-04 13:30:31 | BUILDING PROVISO; 2020 FBC-B 2509.2 BASE FOR TILE. | | | MATERIALS USED AS A BASE FOR WALL TILE IN TUB AND | | | SHOWER AREAS AND WALLS AND CEILING PANELS IN SHOWER | | | AREAS SHALL BE OF MATERIALS LISTED IN TABLE 2509.2 AND | | | INSTALLED IN ACCORDANCE WITH MANUFACTURER?S | | | RECOMMENDATIONS. WATER RESISTANT GYPSUM (MR BOARD) | | | SHALL NOT BE USED FOR SHOWER & TUB ENCLOSURES BUT CAN | | | BE USED FOR BACKING BOARD FOR A BASE FOR TILE IN WATER | | | CLOSET COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE | | | WITH GA-216 OR ASTM C840 AND THE MANUFACTURE?S | | | RECOMMENDATIONS. | | | |
|