| Plan Review Notes For Permit 22070192 |
| Permit Number |
22070192 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-07-11 15:10:57 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 22070192 | | | 7/11/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE PLANS INDICATE A PARTIAL DEMOLITION. CLARIFY IF | | | THE WATER METER AND UTILITY ACCOUNT WILL REMAIN IN | | | PLACE AND ACTIVE, AND IF THE EXISTING BUILDING DRAIN | | | AND SEWER LINE WILL REMAIN. IF THE METER IS TO BE | | | PULLED PLEASE SUBMIT A REQUEST TO THE WPB UTILITIES | | | DEPT. ON THEIR FORM, AND A UTILITY RELEASE FORM. IF THE | | | METER IS TO REMAIN AND THE WATER SERVICE IS TO BE USED | | | DURING DEMOLITION, PLEASE NOTE A BACKFLOW PREVENTION | | | DEVICE IS REQUIRED ON THE SERVICE AND A PERMIT IS | | | REQUIRED FOR THE DEVICE. THE PLUMBING DEMOLITION PERMIT | | | WILL BE APPROVED AFTER THE BACKFLOW PERMIT IS APPROVED. | | | PLEASE SEE THE BUILDING REVIEW COMMENTS FOR FURTHER | | | INFORMATION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|