| Plan Review Notes For Permit 22070178 |
| Permit Number |
22070178 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-07-27 06:18:15 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. FBC 107, SUBMIT THE SURVEY FOR THIS PROPERTY. | | | | | | 2. FBC 107, SHOW THE PROPOSED SITE WALL AND FOUNDATION | | | RELATIVE TO THE PROPERTY LINES. | | | | | | 3. FBC R 301, PROVIDE A STRUCTURAL DETAIL FOR THE | | | PROPOSED WALL. THIS SHOULD INCLUDE WIND DESIGN | | | CRITERIA. | | | | | | 4. THE DRAINAGE PLAN FOR THE HOUSE HAS NOT BEEN | | | REVIEWED. THAT IS NOT WITHIN THE SCOPE OF THIS PERMIT. | | | CLARIFY THAT FILL WILL NOT BE BROUGHT ON SITE UNDER | | | THIS PERMIT, OR RESUBMIT AFTER THE HOUSE DRAINAGE PLAN | | | HAS BEEN REVIEWED AND ACCEPTED, AND NOTE THAT FILL WILL | | | BE BROUGHT IN UNDER THIS PERMIT (CAN BE DONE THROUGH A | | | RESPONSE LETTER). | | | | | | | | | |
|