| 2022-08-10 19:51:50 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | THERE ARE SEVERAL MAJOR CODE VIOLATIONS ON THIS PLAN. |
| | THE PLAN REVIEW HAS BEEN STOPPED. PLEASE KEEP IN MIND |
| | WHEN RESUBMITTING ADDITIONAL VIOLATIONS MAY BE NOTED. |
| | PLEASE LOOK OVER ENTIRE PLAN BEFORE RESUBMITTING. |
| | |
| | |
| | 1. WRONG SERVICE ENTRANCE CONDUCTOR SIZE, ARE YOU |
| | PROPOSING 2 SETS OR 4-300MCM CU COPPER FOR THE SERVICE |
| | MAST? IF SO PLEASE BE MORE CLEAR. NEC 230.23A FBC |
| | 107.2.1 |
| | |
| | 2. 3/4'' CONDUIT NIPPLES TOO SMALL TO METER CENTER FOR |
| | FEEDERS, HOW MANY SETS OF PARALLEL FEEDERS ARE YOU |
| | PROPOSING? AGAIN PLAN IS NOT CLEAR. NEC 300.17 FBC |
| | 107.2.1 |
| | |
| | 3. NO NEUTRAL (GROUNDED CONDUCTOR) BROUGHT TO METER |
| | CENTER NEC 215.2A2 |
| | |
| | 4. WIRES IN SERVICE MAST PER PLAN, 4-#300 CU AND 1-300 |
| | CU NEUTRAL?? PLEASE EXPLAIN THE 5TH WIRE? |
| | |
| | 5. 3/4'' CONDUIT TO HOUSE PANEL IS TO SMALL AND HAS NO |
| | NEUTRAL BROUGHT TO IT. NEC300.17 NEC215.A2 |
| | |
| | 6. SERVICE DISCONNECTING MEANS NOT SHOWN ON FLOOR PLAN |
| | FBC 107.2.1 |
| | |
| | 7. TAMPERPROOF RECEPTACLES REQUIRED PER NEC 406.12 |
| | |
| | 8. AFCI PROTECTION REQUIRED PER NEC 210.12A AND B |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |