| 2022-08-31 16:42:59 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE GENERATOR PAD CALCULATIONS ARE FOR A UNIT THAT | | | THAT WEIGHS 850 LBS. THE GENERATOR SPECIFICATIONS THAT | | | WERE SUBMITTED ARE FOR A UNIT THAT WEIGHS 455 LBS. AND | | | ARE NOT ACCEPTABLE. SUBMIT ENGINEERING CALCULATIONS FOR | | | THE CORRECT SIZE AND WEIGHT UNIT. FBC-R107.2.1 | | | | | | 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 | | | FEET FROM ANY OPENINGS INTO A BUILDING. | | | FBC-R303.5.1 INTAKE OPENINGS.MECHANICAL AND GRAVITY | | | OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS | | | THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS | | | CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, | | | STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | | | | 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
|