2022-08-31 16:42:59PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD CALCULATIONS ARE FOR A UNIT THAT
 THAT WEIGHS 850 LBS. THE GENERATOR SPECIFICATIONS THAT
 WERE SUBMITTED ARE FOR A UNIT THAT WEIGHS 455 LBS. AND
 ARE NOT ACCEPTABLE. SUBMIT ENGINEERING CALCULATIONS FOR
 THE CORRECT SIZE AND WEIGHT UNIT. FBC-R107.2.1
  
 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING.
 FBC-R303.5.1 INTAKE OPENINGS.MECHANICAL AND GRAVITY
 OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS
 THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS
 CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS,
 STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  
 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.