| Plan Review Notes For Permit 22070110 |
| Permit Number |
22070110 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-07-18 09:56:01 | FIRE REVIEW COMMENTS: | | | THE FIRE PUMP SUPPORTING DOCUMENTS ARE NOT PART OF THIS | | | APPROVAL. | | | ALL JOINTS SHALL BE INSPECTED BY THE FIRE DEPARTMENT | | | PRIOR TO COVERING. | | | AT TIME OF INSPECTION, THE CONTRACTOR SHALL HAVE ON | | | SITE THE MANUFACTURES SPECIFICATIONS FOR UNDERGROUND | | | PIPING INCLUDING TORQUE REQUIREMENTS FOR BOLT | | | ASSEMBLIES. | | | C. WALKER | | | 561-804-4762 | | | [email protected] | | | |
|