| Plan Review Notes For Permit 22070110 |
| Permit Number |
22070110 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-07-08 12:23:30 | FIRE REVIEW COMMENTS: | | | INDICATE ON THE PLAN THE DISTANCE FROM THE NEAREST FIRE | | | HYDRANT TO THE FIRE DEPARTMENT CONNECTION (FDC). NFPA | | | 1141 8.1.3 * (2017 EDITION) | | | WHERE MUNICIPAL-TYPE WATER SYSTEMS ARE AVAILABLE, FIRE | | | DEPARTMENT CONNECTIONS FOR SPRINKLER SYSTEMS DESIGNED | | | TO NFPA 13 OR NFPA 13R SHALL BE LOCATED NOT MORE THAN | | | 100 FT (30.5 M) ALONG AN APPROVED PATH FROM A FIRE | | | HYDRANT AND SHALL BE ARRANGED SO THAT HOSE LINES CAN BE | | | READILY AND CONVENIENTLY ATTACHED TO THE INLETS WITHOUT | | | INTERFERENCE FROM ANY NEARBY OBJECTS, INCLUDING | | | BUILDINGS, SIGNS, FENCES, POSTS, OR OTHER FIRE | | | DEPARTMENT CONNECTIONS. | | | PROVIDE SUPPORTING MANUFACTURERS DOCUMENTATION FOR PIPE | | | SPECIFICATIONS, LISTING, BOLT TORQUE SPECIFICATIONS, | | | CORROSION RESISTANCE, ETC. | | | THIS PERMIT APPLIES ONLY TO THE UNDERGROUND FIRE LINE. | | | THE SUPPORTING DOCUMENTS INCLUDED THE FIRE PUMP, THAT | | | IS NOT PART OF THIS PERMIT. | | | ALL JOINTS SHALL BE INSPECTED BY THE FIRE DEPARTMENT | | | PRIOR TO COVERING. | | | OTHER COMMENTS MAY BE FORTHCOMING UPON FURTHER REVIEW. | | | C. WALKER | | | 561-804-4762 | | | [email protected] | | | |
|