| 2023-01-12 16:13:37 | BUILDING REVIEW APPROVED WITH PROVISO |
| | (NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO |
| | INSTALLATION & INSPECTION TO AVOID CONFLICTS/DELAYS): |
| | |
| | (1)SHEET A-01: |
| | (A)PARAPET DETAIL ON SHEET A-01 IS INCOMPLETE. MISSING |
| | CONNECTOR FOR 2X4 SILL PLATE TO THE ROOF RAFTERS AND |
| | ATTACHMENT OF THE DOUBLE 2X4 TOP PLATE TO THE STUDS. |
| | (B)REVISE SIZE OF EMERGENCY OVERFLOW SCUPPERS. SEC. |
| | R903.4.1 FBC-RESIDENTIAL AND SEC. 1108.3 FBC-PLUMBING |
| | (OPENING WIDTH EQUAL TO THE CIRCUMFERENCE OF THE ROOF |
| | DRAIN REQUIRED FOR THE AREA SERVED). |
| | |
| | (2)PRODUCT APPROVALS DEFERRED SUBMITTAL: PROVIDE |
| | PRODUCT APPROVAL FOR: |
| | (A)FLAT ROOF AND CLEARLY MARK/IDENTIFY WHICH ASSEMBLY |
| | IS GOING TO BE INSTALLED. IF SELECTED ASSEMBLY DOESN'T |
| | MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN |
| | SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED. |
| | (B)DOUBLE INSWING FRENCH DOORS AS SHOWN ON THE SECOND |
| | FLOOR. |
| | (C)ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE |
| | USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS |
| | TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC |
| | R301.2.1 FBC-RESIDENTIAL. |
| | (D)ROOF TILE ADHESIVE PRODUCT APPROVAL THAT IS LISTED |
| | ON THE ROOF TILE PRODUCT APPROVAL SUBMITTED. |
| | (E)SLOPED ROOF UNDERLAYMENT. |
| | (3)DESIGNER OF RECORD TO REVIEW AND APPROVE ALL PRODUCT |
| | APPROVALS. |