| 2022-12-28 13:43:46 | ROOFING REVIEW: |
| | |
| | 1- PRODUCT APPROVALS |
| | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 |
| | FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| | |
| | ORIGINAL COMMENT: |
| | A)FLAT ROOF AND CLEARLY MARK/IDENTIFY WHICH ASSEMBLY IS |
| | GOING TO BE INSTALLED. IF SELECTED ASSEMBLY DOESN'T |
| | MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN |
| | SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED. |
| | |
| | RESPONSE: |
| | THERE ARE TWO DIFFERENT PRODUCT APPROVALS UPLOADED IN |
| | THE SAME PDF FILE. ONE IS CERTAINTEED FLORIDA PRODUCT |
| | APPROVAL FL2533-R28 AND THE OTHER ONE IS CERTAINTEED |
| | NOA 17-1003.15. IMPORTANT NEED TO SUBMIT ONLY ONE |
| | PRODUCT APPROVAL TO AVOID CONFLICTS. |
| | |
| | NOTE: |
| | EITHER PRODUCT APPROVAL REQUIRES SIGNED AND SEALED RAS |
| | 117 CALCULATIONS BECAUSE THE SELECTED ASSEMBLIES DON'T |
| | MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES. THE |
| | MAXIMUM DESIGN PRESSURES (MDP) ON SELECTED ASSEMBLY |
| | W-77 CERTAINTEED FLORIDA PRODUCT APPROVAL FL2533-R28 IS |
| | -60PSF. AND THE DESIGN PRESSURES ON CERTAINTEED NOA |
| | 17-1003.15 WERE NO IDENTIFIED BECAUSE NO ASSEMBLY WAS |
| | SELECTED. NEVERTHELESS NONE OF THE ASSEMBLIES ON NOA |
| | SUBMITTED MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES. |
| | NOTE: WHEN SELECTING AN ASSEMBLY MAKE SURE SELECTED |
| | ASSEMBLY IS NOT LIMITED BY GENERAL LIMITATION #9 |
| | BECAUSE THIS LIMITATION DOESN'T ALLOW NAIL ENHANCEMENT. |
| | SEE GENERAL LIMITATION #9 ON LAST PAGE OF NOA. |
| | SEC.107.2.1 CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | B)ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE |
| | USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS |
| | TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC |
| | R301.2.1 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | THERE ARE TWO DIFFERENT PRODUCT APPROVALS UPLOADED IN |
| | THE SAME PDF FILE. ONE IS CERAMICA VEREA FLORIDA |
| | PRODUCT APPROVAL FL17152-R4 AND THE OTHER ONE IS TEJAS |
| | VEREA NOA 20-0902.03. IMPORTANT NEED TO SUBMIT ONLY ONE |
| | PRODUCT APPROVAL AND CLEARLY MARK FASTENING METHOD TO |
| | AVOID CONFLICTS |
| | NOTE: FLORIDA PRODUCT APPROVAL FL17152-R4 IS NOT MARKED |
| | SHOWING THE FASTENING METHOD. NOA 20-0902.03 IS MARKED |
| | WITH AH-160 ADHESIVE ON PAGE 5 OF 9. THIS FASTENING |
| | METHOD IS OK FOR ALL ROOF ZONES BUT ADHESIVE PRODUCT |
| | APPROVAL SUBMITTED DOESN'T MATCH AH-160 ADHESIVE LISTED |
| | IN THE NOA. COORDINATE AS REQUIRED TO AVOID MORE |
| | CONFLICTS/DELAYS. SEC.107.2.1 CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | C)PROVIDE A ROOF TILE ADHESIVE PRODUCT APPROVAL THAT IS |
| | LISTED ON THE ROOF TILE PRODUCT APPROVAL SUBMITTED. |
| | |
| | RESPONSE: |
| | COORDINATE WITH ITEM #9(C) ABOVE TO AVOID MORE |
| | CONFLICTS/DELAYS. SEC.107.2.1 CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | D) HIP AND RIDGE INSTALLATION TO BE USED. AND, CLEARLY |
| | MARK ON PRODUCT APPROVAL ATTACHMENT METHOD. SEC. |
| | R905.3.7.1 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | FLORIDA PRODUCT APPROVAL FL5374-R6 SUBMITTED IS OK. |
| | NOTE: COORDINATE ROOF TILE ADHESIVE WITH ITEM #9(C) |
| | ABOVE TO AVOID MORE CONFLICTS/DELAYS. SEC.107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | |
| | 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |