| 2022-10-05 16:40:07 | RESIDENTIAL (R3) REVISION, ADDITION/ALTERATION SECOND |
| | BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PRMIT #22070105 |
| | 213 MARLBOROUGH RD |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. |
| | ***IMPORTANT****CONTRACTOR TO ADVICE IF PROVISO OPTION |
| | IS PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED |
| | INFORMATION BEFORE PERMIT ISSUANCE. |
| | |
| | |
| | 1- OK. |
| | 2- OK. |
| | 3- OK. |
| | 4- OK. |
| | |
| | ORIGINAL COMMENT: |
| | 5- GUARDRAILS: DESIGNER OF RECORD NEEDS TO PROVIDE THE |
| | DETAILS AND SPECIFICATIONS FOR THE CONSTRUCTION OF THE |
| | BALCONY GUARDRAILS AS REQUIRED BY TABLE R301.5, SEC. |
| | AND SEC. R312.1 FBC-RESIDENTIAL. |
| | NOTE: SUBSEQUENT SHOP DRAWINGS ARE TO CONFIRM THAT |
| | DESIGN DETAILS AND SPECIFICATIONS ARE MET. |
| | |
| | RESPONSE: |
| | PARTIALLY DONE. NO SPECS FOR PICKETS SPACING. ALSO, |
| | GUARDRAIL NOTE ON SHEET A-03 SAYS "SEE STRUCTURAL DWGS |
| | FOR CONNECTION DETAILS (TYP)". INFORMATION WAS NOT |
| | PROVIDED EITHER. |
| | |
| | 6- ARCHITECT IS SPECIFYING R-30 CLOSED CELL SPRAY FOAM |
| | CEILING INSULATION. PROVIDE ICC EVALUATION REPORT FOR |
| | THE ICYNENE R-30 INSULATION TO VERIFY COMPLIANCE WITH |
| | SEC. R316 FBC-RESIDENTIAL. |
| | NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN |
| | WRITING PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | |
| | RESPONSE: |
| | NO SUBMITTED. |
| | |
| | ORIGINAL COMMENT: |
| | 7- PROVIDE COMPLETE FRAMING PLANS, SECTIONS AND |
| | SPECIFICATIONS FOR RE-CONSTRUCTION OF WOOD CORNICE & |
| | BARREL TILE ROOF SHOWN ON PLANS FOR FIRST FLOOR. |
| | SPECIFY ALL FRAMING MEMBERS AND CONNECTORS, ETC. SEC. |
| | R301.2.1 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | PARAPET DETAIL ON SHEET A-01 IS INCOMPLETE. IT DOESN'T |
| | SPECIFY ALL THE FRAMING MEMBERS AND CONNECTORS FOR |
| | PARAPET WALL. NEED TO PROVIDE THIS INFORMATION. |
| | |
| | ORIGINAL COMMENT: |
| | 8- CLARIFY/REVISE SIZE OF EMERGENCY OVERFLOW SCUPPERS |
| | SPECIFIED ON PLANS. SEC. R903.4.1 FBC-RESIDENTIAL. |
| | NOTE: 2" EMERGENCY OVERFLOW SCUPPER DOESN'T COMPLY. |
| | |
| | RESPONSE: |
| | EMERGENCY OVERFLOW SCUPPER SIZE (4"H X 2"W) DOESN'T |
| | COMPLY. SEE SEC. 1108.3 FBC-PLUMBING AS REQUIRED BY |
| | SEC. R903.4.1 FBC-RESIDENTIAL AND REVISE SIZE. |
| | |
| | |
| | 9- PRODUCT APPROVALS |
| | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 |
| | FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| | |
| | ORIGINAL COMMENT: |
| | A)FLAT ROOF AND CLEARLY MARK/IDENTIFY WHICH ASSEMBLY IS |
| | GOING TO BE INSTALLED. IF SELECTED ASSEMBLY DOESN'T |
| | MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN |
| | SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED. |
| | |
| | RESPONSE: |
| | ARCHITECT'S RESPONSE LETTER STATES "GC REVISED FLAT |
| | ROOF SUBMITTAL. NEW SUBMITTAL ATTACHED.". |
| | NOTHING WAS UPLOADED TO PROJECTDOX FOR REVIEW. |
| | |
| | ORIGINAL COMMENT: |
| | B)SINGLE OUTSWING FRENCH DOOR FL34006 SUBMITTED: |
| | INSTALLATION INSTRUCTIONS DRAWING W17-108 SUBMITTED |
| | DON'T MATCH DRAWING HIGHLIGHTED ON THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE. REVISE AS REQUIRED TO MATCH. |
| | NOTE: PLEASE UPLOAD THE FLORIDA PRODUCT APPROVAL COVER |
| | PAGE AND CORRESPONDING INSTALLATION DRAWINGS ON THE |
| | SAME PDF FILE. DO NOT UPLOAD IN SEPARATE FILES. |
| | |
| | RESPONSE: |
| | ARCHITECT'S RESPONSE LETTER STATES "GC REVISED OUTSWING |
| | FRENCH DOOR SUBMITTAL. NEW SUBMITTAL ATTACHED.". |
| | NOTHING WAS UPLOADED TO PROJECTDOX FOR REVIEW. |
| | NOTE: NEED PRODUCT APPROVAL FOR INSWING FRENCH DOORS AS |
| | SHOWN ON THE SECOND FLOOR. CHECK DESIGN PRESSURES |
| | SPECIFIED ON PLANS. |
| | |
| | ORIGINAL COMMENT: |
| | C)ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE |
| | USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS |
| | TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC |
| | R301.2.1 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | ARCHITECT'S RESPONSE LETTER STATES "ROOF TILE AND PADDY |
| | SIZE ADDED. NEW SUBMITTAL ATTACHED.". |
| | NOTHING WAS UPLOADED TO PROJECTDOX FOR REVIEW. |
| | |
| | ORIGINAL COMMENT: |
| | D)PROVIDE A ROOF TILE ADHESIVE PRODUCT APPROVAL THAT IS |
| | LISTED ON THE ROOF TILE PRODUCT APPROVAL SUBMITTED. |
| | |
| | RESPONSE: |
| | ARCHITECT'S RESPONSE LETTER STATES "ROOF TILE ADHESIVE |
| | PRODUCT APPROVAL ATTACHED.". |
| | NOTHING WAS UPLOADED TO PROJECTDOX FOR REVIEW. |
| | |
| | ORIGINAL COMMENT: |
| | E) HIP AND RIDGE INSTALLATION TO BE USED. AND, CLEARLY |
| | MARK ON PRODUCT APPROVAL ATTACHMENT METHOD. SEC. |
| | R905.3.7.1 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | ARCHITECT'S RESPONSE LETTER STATES "HIP AND RIDGE |
| | PRODUCT APPROVAL ATTACHED.". |
| | NOTHING WAS UPLOADED TO PROJECTDOX FOR REVIEW. |
| | |
| | ORIGINAL COMMENT: |
| | 10- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. |
| | NOTE: THIS COMMENT APPLIES TO ALL PRODUCT APPROVALS |
| | SUBMITTED, INCLUDING ONES SUBMITTED EARLIER. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |