| 2022-08-05 18:30:16 | RESIDENTIAL (R3) REVISION, ADDITION/ALTERATION BUILDING |
| | REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22070105 |
| | 213 MARLBOROUGH RD |
| | |
| | NOTE: |
| | CHANGE OF OCCUPANCY SEC. 605 AND SEC. 1001.2.1, SEC. |
| | 604 AND SEC. 901.2, SEC. 801.3 FBC-EXISTING BUILDING. |
| | ALL NEW WORK SHALL COMPLY WITH THE MATERIALS AND |
| | METHODS REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | NOTE: |
| | LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING. |
| | SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3 |
| | FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| | COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| | |
| | |
| | NOTE: THE FOLLOWING COMMENTS ARE BASED ON PLANS |
| | SUBMITTED UNDER MAIN HOUSE REVISION #22070103. WHEN |
| | ADDRESSING THE COMMENTS UNDER THIS PERMIT FOR THE |
| | DETACHED GARAGE, PLEASE SUBMIT ONLY THE DRAWINGS |
| | RELATED TO THE DETACHED GARAGE TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | 1- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW BASED ON ALL SCOPE OF WORK TO BE DONE ON THE |
| | DETACHED GARAGE (SHORING, DEMOLITION AND COMPLETE |
| | RENOVATION). VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS. |
| | PROVIDE COMPLETE COST BREAKDOWN INCLUDING DESIGN |
| | PROFESSIONAL FEES. |
| | |
| | 2- SHEET S-000: |
| | ENGINEER OF RECORD TO REVISE END ZONE DISTANCE "A" |
| | SPECIFIED FOR THE DETACHED GARAGE. THE MINIMUM |
| | DIMENSION IS 4'-0" NOT 3'-0" AS REQUIRED BY NOTE "A" ON |
| | FIGURE R301.2(7) FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| | |
| | 3- CLARIFY/REVISE SIZE SECOND FLOOR ENTRY DOOR (E2). |
| | EXTERIOR DOOR SCHEDULE ON SHEET A-09 SHOWS DOOR E2 AS |
| | 36" X 96" INSWING FRENCH DOOR, BUT |
| | SECOND FLOOR PLAN ON SHEET A-02.1 CALL FOR 2'-10" DOOR |
| | OPENING. REVISE AS REQUIRED TO MATCH. NEED TO VERIFY |
| | ENTRY DOOR COMPLIANCE WITH EGRESS SEC. R311.2 |
| | FBC-RESIDENTIAL. |
| | |
| | 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | RECONSTRUCTION OF THE STAIRWAY SHOWING COMPLIANCE WITH |
| | SEC. R311.7 FBC-RESIDENTIAL. |
| | PROVIDE SPECS FOR STAIRWAY CONSTRUCTION AND SHOW |
| | HANDRAIL LOCATION AND HEIGHT, RISER AND TREADS |
| | DIMENSIONS INCLUDING NOSING. |
| | |
| | 5- GUARDRAILS: DESIGNER OF RECORD NEEDS TO PROVIDE THE |
| | DETAILS AND SPECIFICATIONS FOR THE CONSTRUCTION OF THE |
| | BALCONY GUARDRAILS AS REQUIRED BY TABLE R301.5, SEC. |
| | AND SEC. R312.1 FBC-RESIDENTIAL. |
| | NOTE: SUBSEQUENT SHOP DRAWINGS ARE TO CONFIRM THAT |
| | DESIGN DETAILS AND SPECIFICATIONS ARE MET. |
| | |
| | 6- ARCHITECT IS SPECIFYING R-30 CLOSED CELL SPRAY FOAM |
| | CEILING INSULATION. PROVIDE ICC EVALUATION REPORT FOR |
| | THE ICYNENE R-30 INSULATION TO VERIFY COMPLIANCE WITH |
| | SEC. R316 FBC-RESIDENTIAL. |
| | NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN |
| | WRITING PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | |
| | 7- PROVIDE COMPLETE FRAMING PLANS, SECTIONS AND |
| | SPECIFICATIONS FOR RE-CONSTRUCTION OF WOOD CORNICE & |
| | BARREL TILE ROOF SHOWN ON PLANS. SPECIFY ALL FRAMING |
| | MEMBERS AND CONNECTORS, ETC. SEC. R301.2.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 8- CLARIFY/REVISE SIZE OF EMERGENCY OVERFLOW SCUPPERS |
| | SPECIFIED ON PLANS. SEC. R903.4.1 FBC-RESIDENTIAL. |
| | NOTE: 2" EMERGENCY OVERFLOW SCUPPER DOESN'T COMPLY. |
| | |
| | 9- PRODUCT APPROVALS |
| | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 |
| | FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| | |
| | A)FLAT ROOF AND CLEARLY MARK/IDENTIFY WHICH ASSEMBLY IS |
| | GOING TO BE INSTALLED. IF SELECTED ASSEMBLY DOESN'T |
| | MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN |
| | SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED. |
| | |
| | B)SINGLE OUTSWING FRENCH DOOR FL34006 SUBMITTED: |
| | INSTALLATION INSTRUCTIONS DRAWING W17-108 SUBMITTED |
| | DON'T MATCH DRAWING HIGHLIGHTED ON THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE. REVISE AS REQUIRED TO MATCH. |
| | NOTE: PLEASE UPLOAD THE FLORIDA PRODUCT APPROVAL COVER |
| | PAGE AND CORRESPONDING INSTALLATION DRAWINGS ON THE |
| | SAME PDF FILE. DO NOT UPLOAD IN SEPARATE FILES. |
| | |
| | C)ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE |
| | USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS |
| | TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC |
| | R301.2.1 FBC-RESIDENTIAL. |
| | |
| | D)PROVIDE A ROOF TILE ADHESIVE PRODUCT APPROVAL THAT IS |
| | LISTED ON THE ROOF TILE PRODUCT APPROVAL SUBMITTED. |
| | |
| | E) HIP AND RIDGE INSTALLATION TO BE USED. AND, CLEARLY |
| | MARK ON PRODUCT APPROVAL ATTACHMENT METHOD. SEC. |
| | R905.3.7.1 FBC-RESIDENTIAL. |
| | |
| | F)WINDOW MULLIONS NOA 19-0131.11 SUBMITTED. NOTE: NEED |
| | TO SPECIFY MULLION SIZE TO VERIFY PRESSURES. SEC. |
| | R301.2.1 FBC-RESIDENTIAL. |
| | |
| | 10- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |