Plan Review Notes
Plan Review Notes For Permit 22070105
Permit Number 22070105
Review Stop B
Sequence Number 1
Notes
Date Text
2022-08-05 18:30:16RESIDENTIAL (R3) REVISION, ADDITION/ALTERATION BUILDING
 REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22070105
 213 MARLBOROUGH RD
  
 NOTE:
 CHANGE OF OCCUPANCY SEC. 605 AND SEC. 1001.2.1, SEC.
 604 AND SEC. 901.2, SEC. 801.3 FBC-EXISTING BUILDING.
 ALL NEW WORK SHALL COMPLY WITH THE MATERIALS AND
 METHODS REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
  
 NOTE: THE FOLLOWING COMMENTS ARE BASED ON PLANS
 SUBMITTED UNDER MAIN HOUSE REVISION #22070103. WHEN
 ADDRESSING THE COMMENTS UNDER THIS PERMIT FOR THE
 DETACHED GARAGE, PLEASE SUBMIT ONLY THE DRAWINGS
 RELATED TO THE DETACHED GARAGE TO AVOID
 CONFLICTS/DELAYS.
  
 1- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW BASED ON ALL SCOPE OF WORK TO BE DONE ON THE
 DETACHED GARAGE (SHORING, DEMOLITION AND COMPLETE
 RENOVATION). VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS.
 PROVIDE COMPLETE COST BREAKDOWN INCLUDING DESIGN
 PROFESSIONAL FEES.
  
 2- SHEET S-000:
 ENGINEER OF RECORD TO REVISE END ZONE DISTANCE "A"
 SPECIFIED FOR THE DETACHED GARAGE. THE MINIMUM
 DIMENSION IS 4'-0" NOT 3'-0" AS REQUIRED BY NOTE "A" ON
 FIGURE R301.2(7) FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 3- CLARIFY/REVISE SIZE SECOND FLOOR ENTRY DOOR (E2).
 EXTERIOR DOOR SCHEDULE ON SHEET A-09 SHOWS DOOR E2 AS
 36" X 96" INSWING FRENCH DOOR, BUT
 SECOND FLOOR PLAN ON SHEET A-02.1 CALL FOR 2'-10" DOOR
 OPENING. REVISE AS REQUIRED TO MATCH. NEED TO VERIFY
 ENTRY DOOR COMPLIANCE WITH EGRESS SEC. R311.2
 FBC-RESIDENTIAL.
  
 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 RECONSTRUCTION OF THE STAIRWAY SHOWING COMPLIANCE WITH
 SEC. R311.7 FBC-RESIDENTIAL.
 PROVIDE SPECS FOR STAIRWAY CONSTRUCTION AND SHOW
 HANDRAIL LOCATION AND HEIGHT, RISER AND TREADS
 DIMENSIONS INCLUDING NOSING.
  
 5- GUARDRAILS: DESIGNER OF RECORD NEEDS TO PROVIDE THE
 DETAILS AND SPECIFICATIONS FOR THE CONSTRUCTION OF THE
 BALCONY GUARDRAILS AS REQUIRED BY TABLE R301.5, SEC.
 AND SEC. R312.1 FBC-RESIDENTIAL.
 NOTE: SUBSEQUENT SHOP DRAWINGS ARE TO CONFIRM THAT
 DESIGN DETAILS AND SPECIFICATIONS ARE MET.
  
 6- ARCHITECT IS SPECIFYING R-30 CLOSED CELL SPRAY FOAM
 CEILING INSULATION. PROVIDE ICC EVALUATION REPORT FOR
 THE ICYNENE R-30 INSULATION TO VERIFY COMPLIANCE WITH
 SEC. R316 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 7- PROVIDE COMPLETE FRAMING PLANS, SECTIONS AND
 SPECIFICATIONS FOR RE-CONSTRUCTION OF WOOD CORNICE &
 BARREL TILE ROOF SHOWN ON PLANS. SPECIFY ALL FRAMING
 MEMBERS AND CONNECTORS, ETC. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 8- CLARIFY/REVISE SIZE OF EMERGENCY OVERFLOW SCUPPERS
 SPECIFIED ON PLANS. SEC. R903.4.1 FBC-RESIDENTIAL.
 NOTE: 2" EMERGENCY OVERFLOW SCUPPER DOESN'T COMPLY.
  
 9- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)FLAT ROOF AND CLEARLY MARK/IDENTIFY WHICH ASSEMBLY IS
 GOING TO BE INSTALLED. IF SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN
 SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
  
 B)SINGLE OUTSWING FRENCH DOOR FL34006 SUBMITTED:
 INSTALLATION INSTRUCTIONS DRAWING W17-108 SUBMITTED
 DON'T MATCH DRAWING HIGHLIGHTED ON THE FLORIDA PRODUCT
 APPROVAL COVER PAGE. REVISE AS REQUIRED TO MATCH.
 NOTE: PLEASE UPLOAD THE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND CORRESPONDING INSTALLATION DRAWINGS ON THE
 SAME PDF FILE. DO NOT UPLOAD IN SEPARATE FILES.
  
 C)ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE
 USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC
 R301.2.1 FBC-RESIDENTIAL.
  
 D)PROVIDE A ROOF TILE ADHESIVE PRODUCT APPROVAL THAT IS
 LISTED ON THE ROOF TILE PRODUCT APPROVAL SUBMITTED.
  
 E) HIP AND RIDGE INSTALLATION TO BE USED. AND, CLEARLY
 MARK ON PRODUCT APPROVAL ATTACHMENT METHOD. SEC.
 R905.3.7.1 FBC-RESIDENTIAL.
  
 F)WINDOW MULLIONS NOA 19-0131.11 SUBMITTED. NOTE: NEED
 TO SPECIFY MULLION SIZE TO VERIFY PRESSURES. SEC.
 R301.2.1 FBC-RESIDENTIAL.
  
 10- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]