| Date |
Text |
| 2023-03-08 16:41:00 | NOTE: |
| | THERE ARE ROOFING SUBPERMITS FOR THIS PROJECT. TO AVOID |
| | CONFLICTS/DELAYS AND TO EXPEDITE THE BUILDING REVIEW |
| | PROCESS IT WILL BE BETTER TO SUBMIT ALL THE ROOFING |
| | PRODUCT APPROVALS ALONG WITH THE ROOFING PERMITS. |
| | |
| | |
| | ROOFING REVIEW: |
| | |
| | NOTE; ITEM #1 WILL BE REVIEWED ONCE DESIGN PRESSURES |
| | ARE REVISED. SEE ITEM #4 ABOVE. PLEASE MAKE SURE BELOW |
| | COMMENTS FOR EACH PRODUCT APPROVAL IS ADDRESSED TO |
| | AVOID CONFLICTS/DELAYS. |
| | |
| | 1- PRODUCT APPROVALS |
| | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 |
| | FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| | |
| | A) FLAT ROOF AND CLEARLY MARK/IDENTIFY WHICH ASSEMBLY |
| | IS GOING TO BE INSTALLED. IF SELECTED ASSEMBLY DOESN'T |
| | MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN |
| | SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED. |
| | NOTE: THERE ARE DIFFERENT TYPES OF CONSTRUCTION IN THIS |
| | HOUSE. CONCRETE ROOF (NEW TERRACE) AND WOOD FRAMED |
| | (EXISTING ROOFS). ALSO, THERE ARE SOME FLAT ROOF TO BE |
| | COVERED WITH TILE AND THERE IS THE MAIN ROOF, NOT A |
| | DECK. PROVIDE PRODUCT APPROVAL COMPATIBLE EACH PROPOSED |
| | APPLICATION. |
| | |
| | B) ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE |
| | USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS |
| | TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC |
| | R301.2.1 FBC-RESIDENTIAL. |
| | |
| | C)PROVIDE A ROOF TILE ADHESIVE PRODUCT APPROVAL THAT IS |
| | LISTED ON THE ROOF TILE PRODUCT APPROVAL SUBMITTED. |
| | |
| | D) HIP AND RIDGE INSTALLATION TO BE USED. AND, CLEARLY |
| | MARK ON PRODUCT APPROVAL ATTACHMENT METHOD. SEC. |
| | R905.3.7.1 FBC-RESIDENTIAL. |
| | |
| | 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | TO BE COORDINATED WITH ITEM #1 ABOVE. PLEASE MAKE SURE |
| | ALL PRODUCT APPROVALS ARE REVIEWED/APPROVED TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |