| 2023-03-08 16:39:34 | RESIDENTIAL (R3) REVISION, THIRD BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | REVISION #22070103 |
| | 211 MARLBOROUGH RD |
| | |
| | PREVIOUS COMMENT: |
| | 9- PROVIDE COMPLETE FRAMING PLANS FOR NEW 30"X96" |
| | SKYLIGHT AND FOR NEW SOLAR TUBES. SEC. R301.2.1 |
| | FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NO ADDRESSED. PROVIDE COMPLETE FRAMING |
| | DETAILS. PROVIDE ROOF FRAMING PLAN AND SPECIFY ALL |
| | FRAMING MEMBERS & CONNECTORS. |
| | |
| | 11- PRODUCT APPROVALS |
| | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 |
| | FOR: |
| | |
| | PREVIOUS COMMENT: |
| | A)SOLATUBE FLORIDA PRODUCT APPROVAL SUBMITTED |
| | (FL11480-R13) DOESN'T MEET THE DESIGN PRESSURES |
| | CALCULATED BY THE ENGINEER OF RECORD ON SHEET S-000. |
| | NEED TO PROVIDE PRODUCT APPROVAL THAT MEETS OR EXCEEDS |
| | CALCULATED DESIGN PRESSURES. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | PREVIOUS COMMENT: |
| | B)SKYLIGHT (30"X96") NOA 20-1013.05 SUBMITTED DOESN'T |
| | MEET THE DESIGN PRESSURES CALCULATED BY THE ENGINEER OF |
| | RECORD ON SHEET S-000. NEED TO PROVIDE PRODUCT APPROVAL |
| | THAT MEETS OR EXCEEDS CALCULATED DESIGN PRESSURES. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | PREVIOUS COMMENT: |
| | D)WINDOW MULLIONS FLORIDA PRODUCT APPROVAL FL34545 |
| | SUBMITTED. NOTE: NEED TO SPECIFY MULLION SIZE TO VERIFY |
| | PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | PREVIOUS COMMENT: |
| | E)FIXED WINDOW FLORIDA PRODUCT APPROVAL FL34706 |
| | SUBMITTED: SHEET 2 OF 7 OF INSTALLATION DRAWINGS SHOWS |
| | TYPE GLASS "B" TO BE USED. THIS TYPE OF GLASS IS NOT |
| | COVERED IN THE DESIGN LOADS CAPACITY TABLES FOR 4"-2" X |
| | 6'-10" WINDOW "A1" SPECIFIED ON SHEET A-09. SEE SHEETS |
| | 3 OF 7 AND 4 OF 7 OF INSTALLATION DRAWINGS AND REVISE |
| | AS REQUIRED OR PROVIDE PRODUCT APPROVAL THAT WORKS TO |
| | MEET THE CALCULATED DESIGN PRESSURES. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | PREVIOUS COMMENT: |
| | F)FLAT ROOF AND CLEARLY MARK/IDENTIFY WHICH ASSEMBLY IS |
| | GOING TO BE INSTALLED. IF SELECTED ASSEMBLY DOESN'T |
| | MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN |
| | SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED. |
| | NOTE: THERE ARE DIFFERENT TYPES OF CONSTRUCTION IN THIS |
| | HOUSE. CONCRETE ROOF (NEW TERRACE) AND WOOD FRAMED |
| | (EXISTING ROOFS). ALSO, THERE ARE SOME FLAT ROOF TO BE |
| | COVERED WITH TILE AND THERE IS THE MAIN ROOF, NOT A |
| | DECK. PROVIDE PRODUCT APPROVAL COMPATIBLE EACH PROPOSED |
| | APPLICATION. |
| | |
| | RESPONSE: |
| | THE DESIGN PRESSURES OF SELECTED SYSTEM W-77 ON PAGE 15 |
| | OF 20 OF FLORIDA PRODUCT APPROVAL FL2533-R28 SUBMITTED |
| | DON'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES. |
| | NEED TO PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS |
| | AS REQUIRED BY LIMITATION 5.7.2 OF PAGE 5 OF 5 OF |
| | PRODUCT APPROVAL SUBMITTED. |
| | |
| | NOTE: |
| | THERE ARE ROOFING SUBPERMITS FOR THIS PROJECT. TO AVOID |
| | CONFLICTS/DELAYS AND TO EXPEDITE THE BUILDING REVIEW |
| | PROCESS IT WILL BE BETTER TO SUBMIT ALL THE ROOFING |
| | PRODUCT APPROVALS ALONG WITH THE ROOFING PERMITS. |
| | |
| | PREVIOUS COMMENT: |
| | G) ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE |
| | USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS |
| | TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC |
| | R301.2.1 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | SEE NOTE ABOVE REGARDING ROOF PRODUCT APPROVALS. |
| | |
| | PREVIOUS COMMENT: |
| | H)PROVIDE A ROOF TILE ADHESIVE PRODUCT APPROVAL THAT IS |
| | LISTED ON THE ROOF TILE PRODUCT APPROVAL SUBMITTED. |
| | |
| | RESPONSE: |
| | SEE NOTE ABOVE REGARDING ROOF PRODUCT APPROVALS. |
| | |
| | PREVIOUS COMMENT: |
| | I) HIP AND RIDGE INSTALLATION TO BE USED. AND, CLEARLY |
| | MARK ON PRODUCT APPROVAL ATTACHMENT METHOD. SEC. |
| | R905.3.7.1 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | SEE NOTE ABOVE REGARDING ROOF PRODUCT APPROVALS. |
| | |
| | 12-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL REVISED PRODUCT APPROVALS |
| | AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |