2022-11-08 15:16:14RESIDENTIAL (R3) REVISION, SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 REVISION #22070103 211 MARLBOROUGH RD
  
 1- OK.
 2- OK.
  
 3- OK. CBAA CASE #1455 WAS APPROVED.
  
 ORIGINAL COMMENT:
 4- WINDOWS AND DOORS DESIGN PRESSURES SHOWN ON THE
 ARCHITECTURAL EXTERIOR ELEVATIONS DON'T MATCH THE
 DESIGN PRESSURES CALCULATED BY THE STRUCTURAL ENGINEER.
 REVISE AS REQUIRED TO MATCH. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 DESIGN PRESSURES WERE REMOVED FROM THE ENGINEER'S
 DRAWINGS. DESIGN PRESSURES SHOWN ON THE ARCHITECTURAL
 PLANS ARE TOO LOW FOR BUILDING LOCATED IN EXPOSURE "D"
 AS SPECIFIED BY THE ENGINEER OF RECORD UNDER THE WIND
 DESIGN DATA. REVISE AS REQUIRED. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 5- OK.
 6- OK.
 7- OK.
 8- OK.
  
 ORIGINAL COMMENT:
 9- PROVIDE COMPLETE FRAMING PLANS FOR NEW 30"X96"
 SKYLIGHT AND FOR NEW SOLAR TUBES. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 ARCHITECT'S RESPONSE LETTER SAYS FRAMING DETAILS HAVE
 BEEN ADDED TO STRUCTURAL DRAWINGS. STRUCTURAL DRAWINGS
 SAYS SKYLIGHT SEE ARCH ???L DRAWINGS. INFORMATION WAS
 NOT PROVIDED. PROVIDE COMPLETE FRAMING DETAILS. SPECIFY
 ALL FRAMING MEMBERS & CONNECTORS.
  
 ORIGINAL COMMENT:
 10- GUARDRAILS: DESIGNER OF RECORD NEEDS TO PROVIDE THE
 DETAILS AND SPECIFICATIONS FOR THE CONSTRUCTION OF THE
 BALCONY AND TERRACE GUARDRAILS AS REQUIRED BY TABLE
 R301.5, SEC. AND SEC. R312.1 FBC-RESIDENTIAL.
 NOTE: SUBSEQUENT SHOP DRAWINGS ARE TO CONFIRM THAT
 DESIGN DETAILS AND SPECIFICATIONS ARE MET.
  
 RESPONSE:
 ARCHITECTURAL PLANS SAYS SEE STRUCTURAL DRAWINGS.
 STRUCTURAL DRAWINGS SAYS SEE ARCHITECTURAL DRAWINGS.
 INFORMATION WAS NOT SUBMITTED.
  
 NOTE; ITEM #11 WILL BE REVIEWED ONCE DESIGN PRESSURES
 ARE REVISED. SEE ITEM #4 ABOVE. PLEASE MAKE SURE BELOW
 COMMENTS FOR EACH PRODUCT APPROVAL IS ADDRESSED TO
 AVOID CONFLICTS/DELAYS.
 11- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)SOLATUBE FLORIDA PRODUCT APPROVAL SUBMITTED
 (FL11480-R13) DOESN'T MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD ON SHEET S-000.
 NEED TO PROVIDE PRODUCT APPROVAL THAT MEETS OR EXCEEDS
 CALCULATED DESIGN PRESSURES.
  
 B)SKYLIGHT (30"X96") NOA 20-1013.05 SUBMITTED DOESN'T
 MEET THE DESIGN PRESSURES CALCULATED BY THE ENGINEER OF
 RECORD ON SHEET S-000. NEED TO PROVIDE PRODUCT APPROVAL
 THAT MEETS OR EXCEEDS CALCULATED DESIGN PRESSURES.
  
 C)SINGLE OUTSWING FRENCH DOOR FL34006 SUBMITTED DOESN'T
 MEET THE DESIGN PRESSURES CALCULATED BY THE ENGINEER OF
 RECORD ON SHEET S-200. NEED TO PROVIDE PRODUCT APPROVAL
 THAT MEETS OR EXCEEDS CALCULATED DESIGN PRESSURES.
 NOTE: PLEASE UPLOAD THE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND CORRESPONDING INSTALLATION DRAWINGS ON THE
 SAME PDF FILE. DO NOT UPLOAD IN SEPARATE FILES.
  
 D)WINDOW MULLIONS FLORIDA PRODUCT APPROVAL FL34545
 SUBMITTED. NOTE: NEED TO SPECIFY MULLION SIZE TO VERIFY
 PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 E)FIXED WINDOW FLORIDA PRODUCT APPROVAL FL34706
 SUBMITTED: SHEET 2 OF 7 OF INSTALLATION DRAWINGS SHOWS
 TYPE GLASS "B" TO BE USED. THIS TYPE OF GLASS IS NOT
 COVERED IN THE DESIGN LOADS CAPACITY TABLES FOR 4"-2" X
 6'-10" WINDOW "A1" SPECIFIED ON SHEET A-09. SEE SHEETS
 3 OF 7 AND 4 OF 7 OF INSTALLATION DRAWINGS AND REVISE
 AS REQUIRED OR PROVIDE PRODUCT APPROVAL THAT WORKS TO
 MEET THE CALCULATED DESIGN PRESSURES.
  
 F)FLAT ROOF AND CLEARLY MARK/IDENTIFY WHICH ASSEMBLY IS
 GOING TO BE INSTALLED. IF SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN
 SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
 NOTE: THERE ARE DIFFERENT TYPES OF CONSTRUCTION IN THIS
 HOUSE. CONCRETE ROOF (NEW TERRACE) AND WOOD FRAMED
 (EXISTING ROOFS). ALSO, THERE ARE SOME FLAT ROOF TO BE
 COVERED WITH TILE AND THERE IS THE MAIN ROOF, NOT A
 DECK. PROVIDE PRODUCT APPROVAL COMPATIBLE EACH PROPOSED
 APPLICATION.
  
 G) ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE
 USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC
 R301.2.1 FBC-RESIDENTIAL.
  
 H)PROVIDE A ROOF TILE ADHESIVE PRODUCT APPROVAL THAT IS
 LISTED ON THE ROOF TILE PRODUCT APPROVAL SUBMITTED.
  
 I) HIP AND RIDGE INSTALLATION TO BE USED. AND, CLEARLY
 MARK ON PRODUCT APPROVAL ATTACHMENT METHOD. SEC.
 R905.3.7.1 FBC-RESIDENTIAL.
  
 12-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 TO BE COORDINATED WITH ITEM #11 ABOVE. PLEASE MAKE SURE
 ALL PRODUCT APPROVALS ARE REVIEWED/APPROVED TO AVOID
 CONFLICTS/DELAYS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,