| Date |
Text |
| 2022-07-25 15:21:29 | 1ST REVIEW FBC-2020 RES. PLUMBING |
| | PERMIT- 22070103 |
| | 7/25/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) P-01.1 & P-01.2: A SEPARATE PRIMARY PERMIT AND |
| | SUB-PERMITS UNDER THE PRIMARY ARE REQUIRED FOR THE |
| | GARAGE CONVERSION TO GUEST HOUSE- SEC. 105.1 & 107.2.1 |
| | WPB. |
| | |
| | 2) P-01.1 & P-01.2: TWO DWELLINGS ON THE SAME LOT WILL |
| | REQUIRE WATER USERS TO INSTALL A BACKFLOW PREVENTION |
| | ASSEMBLY AT THE POINT OF DELIVERY. A REDUCED PRESSURE |
| | ZONE BACKFLOW DEVICE WILL BE REQUIRED FOR THE WATER |
| | METER PER SECS. C, D & E- CITY OF WEST PALM CROSS |
| | UTILITIES CROSS-CONNECTION CONTROL MANUAL. |
| | PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR |
| | SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE |
| | BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB |
| | AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL |
| | BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| | |
| | 3) P-01.1 & P-01.2: PLEASE SHOW THE SOURCE OF THE HOT |
| | WATER FOR THE NEW FIXTURES IN THE GUEST HOUSE- SEC. |
| | P2801.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |