2022-07-25 11:25:30ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE ALL ELECTRIC METER, ATS, DISCONNECT,
 AND PANEL EQUIPMENT LOCATIONS ON SITE AND FLOOR PLANS.
 107.2
 2) PLEASE DETAIL COMPLIANCE WITH NEC 225.30 FOR GARAGE
 BUILDING FEEDERS
 3) PLEASE PROVIDE DETAILS ON COMPLIANCE WITH NEC 250.32
 PROVISIONS FOR GROUNDING ELECTRODE SYSTEM AT GARAGE
 SEPARATE BUILDING
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  