Plan Review Notes
Plan Review Notes For Permit 22070103
Permit Number 22070103
Review Stop B
Sequence Number 1
Notes
Date Text
2022-08-05 15:00:57RESIDENTIAL (R3) REVISION, ADDITION/ALTERATION BUILDING
 REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 REVISION #22070103 211 MARLBOROUGH RD
  
 NOTE:
 ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
  
 COMMENTS FOR MAIN HOUSE REVISION ONLY (NOTE: DETACHED
 GARAGE REVIEW DONE UNDER PERMIT #22070105):
 1- THIS REVISION IS ONLY FOR THE WORK AT THE MAIN
 HOUSE. ALL THE PLANS SUBMITTED FOR WORK AT THE TWO
 STORY DETACHED GARAGE NEEDS TO BE SUBMITTED UNDER
 SEPARATE PERMIT. THIS IS REQUIRED IN ORDER TO AVOID
 CONFLICTS AND FOR PROPER TRACKING AND RECORDS
 MANAGEMENT SINCE THE DETACHED GARAGE HAS A DIFFERENT
 ADDRESS. THERE IS ALREADY A SEPARATE PERMIT FOR THE
 DETACHED GARAGE. SEE PERMIT #22070105. SEC. 107.2.1.3
 CITY AMENDMENTS.
 NOTE: SINCE OTHER PLAN REVIEWERS MADE COMMENTS RELATING
 TO THE GARAGE, THEN PLEASE MAKE SURE TO ADDRESS GARAGE
 COMMENTS ON PERMIT 22070105 WHEN RESUBMITTING. THIS
 WILL AVOID MORE CONFLICTS/DELAYS.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION FOR THE
 ADDITIONAL WORK IS TOO LOW. VALUATION TO INCLUDE ALL
 LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND
 DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS.
 PROVIDE COMPLETE COST BREAKDOWN INCLUDING DESIGN
 PROFESSIONAL FEES.
  
 3- THIS HOUSE IS LOCATED IN FLOOD ZONE AE WITH A BASE
 FLOOD ELEVATION (BFE) OF 6 FEET BASED ON NAVD 88. IT
 LOOKS LIKE THE PROPOSED ADDITION AND ADDITIONAL WORK TO
 THE EXISTING MAIN HOUSE IS CONSIDERED A SUBSTANTIAL
 IMPROVEMENT. THE ADDITION AND THE EXISTING HOUSE SHALL
 HAVE THE LOWEST FLOOR FINISHED ELEVATION ELEVATED TO OR
 ABOVE THE BASE FLOOD ELEVATION PLUS TWO FEET.
 THEREFORE, THE MIN. REQUIRED FINISHED FLOOR ELEVATION
 IS 8 FEET. CITY ORDINANCE 4729-17. SEC. 18-33 TECHNICAL
 AMENDMENTS TO FLORIDA BUILDING CODE. SEC. 107.3.5.3
 CITY AMENDMENTS.
 PLANS NEED TO SHOW THE PROPOSED FINISHED FLOOR
 ELEVATION. NEED TO PROVIDE THE CONSTRUCTION DRAWINGS
 ELEVATION CERTIFICATE AND SURVEY SHOWING THE FINISH
 FLOOR ELEVATIONS FOR REVIEW.
  
 DURING THE PERMITTING OF THIS STRUCTURE THREE DIFFERENT
 FLOOD ELEVATION CERTIFICATES WILL BE REQUIRED:
 A) CONSTRUCTION DRAWINGS.
 B) BUILDING UNDER CONSTRUCTION.
 C) FINISHED CONSTRUCTION.
  
 4- WINDOWS AND DOORS DESIGN PRESSURES SHOWN ON THE
 ARCHITECTURAL EXTERIOR ELEVATIONS DON'T MATCH THE
 DESIGN PRESSURES CALCULATED BY THE STRUCTURAL ENGINEER.
 REVISE AS REQUIRED TO MATCH. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 5- PROVIDE COMPLETE FRAMING PLANS, SECTIONS AND
 SPECIFICATIONS FOR CONSTRUCTION OF NEW CHIMNEY ON REAR
 PORCH AND TERRACE ABOVE. SPECIFY ALL FRAMING MEMBERS
 AND CONNECTORS, SPECIFY ALL EXTERIOR WALL COMPONENTS.
 SEC. R301.2.1 FBC-RESIDENTIAL.
 NOTE: STRUCTURAL PLANS DON'T SHOW OPENING ON TERRACE
 CONCRETE SLAB.
  
 6- PROVIDE COMPLETE FRAMING PLANS, SECTIONS AND
 SPECIFICATIONS FOR CONSTRUCTION OF NEW WOOD CORNICE &
 BARREL TILE ROOF SHOWN ON THE WEST ELEVATION. SPECIFY
 ALL FRAMING MEMBERS AND CONNECTORS, ETC. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 7- CLARIFY/REVISE SIZE OF EMERGENCY OVERFLOW SCUPPERS
 SPECIFIED ON SHEET A-02.1 TO SHOW COMPLIANCE WITH SEC.
 R903.4.1 FBC-RESIDENTIAL.
 2" EMERGENCY OVERFLOW SCUPPER DOESN'T COMPLY.
  
 8- SPECIFY CARBON MONOXIDE ALARM WITHIN ALL SLEEPING
 ROOMS, INCLUDING EXISTING BEDROOMS AS REQUIRED BY SEC.
 R315.1 FBC-RESIDENTIAL.
  
 9- PROVIDE COMPLETE FRAMING PLANS FOR NEW 30"X96"
 SKYLIGHT AND FOR NEW SOLAR TUBES. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 10- GUARDRAILS: DESIGNER OF RECORD NEEDS TO PROVIDE THE
 DETAILS AND SPECIFICATIONS FOR THE CONSTRUCTION OF THE
 BALCONY AND TERRACE GUARDRAILS AS REQUIRED BY TABLE
 R301.5, SEC. AND SEC. R312.1 FBC-RESIDENTIAL.
 NOTE: SUBSEQUENT SHOP DRAWINGS ARE TO CONFIRM THAT
 DESIGN DETAILS AND SPECIFICATIONS ARE MET.
  
 11- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)SOLATUBE FLORIDA PRODUCT APPROVAL SUBMITTED
 (FL11480-R13) DOESN'T MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD ON SHEET S-000.
 NEED TO PROVIDE PRODUCT APPROVAL THAT MEETS OR EXCEEDS
 CALCULATED DESIGN PRESSURES.
  
 B)SKYLIGHT (30"X96") NOA 20-1013.05 SUBMITTED DOESN'T
 MEET THE DESIGN PRESSURES CALCULATED BY THE ENGINEER OF
 RECORD ON SHEET S-000. NEED TO PROVIDE PRODUCT APPROVAL
 THAT MEETS OR EXCEEDS CALCULATED DESIGN PRESSURES.
  
 C)SINGLE OUTSWING FRENCH DOOR FL34006 SUBMITTED DOESN'T
 MEET THE DESIGN PRESSURES CALCULATED BY THE ENGINEER OF
 RECORD ON SHEET S-200. NEED TO PROVIDE PRODUCT APPROVAL
 THAT MEETS OR EXCEEDS CALCULATED DESIGN PRESSURES.
 NOTE: PLEASE UPLOAD THE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND CORRESPONDING INSTALLATION DRAWINGS ON THE
 SAME PDF FILE. DO NOT UPLOAD IN SEPARATE FILES.
  
 D)WINDOW MULLIONS FLORIDA PRODUCT APPROVAL FL34545
 SUBMITTED. NOTE: NEED TO SPECIFY MULLION SIZE TO VERIFY
 PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 E)FIXED WINDOW FLORIDA PRODUCT APPROVAL FL34706
 SUBMITTED: SHEET 2 OF 7 OF INSTALLATION DRAWINGS SHOWS
 TYPE GLASS "B" TO BE USED. THIS TYPE OF GLASS IS NOT
 COVERED IN THE DESIGN LOADS CAPACITY TABLES FOR 4"-2" X
 6'-10" WINDOW "A1" SPECIFIED ON SHEET A-09. SEE SHEETS
 3 OF 7 AND 4 OF 7 OF INSTALLATION DRAWINGS AND REVISE
 AS REQUIRED OR PROVIDE PRODUCT APPROVAL THAT WORKS TO
 MEET THE CALCULATED DESIGN PRESSURES.
  
 F)FLAT ROOF AND CLEARLY MARK/IDENTIFY WHICH ASSEMBLY IS
 GOING TO BE INSTALLED. IF SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN
 SIGNED AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
 NOTE: THERE ARE DIFFERENT TYPES OF CONSTRUCTION IN THIS
 HOUSE. CONCRETE ROOF (NEW TERRACE) AND WOOD FRAMED
 (EXISTING ROOFS). ALSO, THERE ARE SOME FLAT ROOF TO BE
 COVERED WITH TILE AND THERE IS THE MAIN ROOF, NOT A
 DECK. PROVIDE PRODUCT APPROVAL COMPATIBLE EACH PROPOSED
 APPLICATION.
  
 G) ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE
 USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC
 R301.2.1 FBC-RESIDENTIAL.
  
 H)PROVIDE A ROOF TILE ADHESIVE PRODUCT APPROVAL THAT IS
 LISTED ON THE ROOF TILE PRODUCT APPROVAL SUBMITTED.
  
 I) HIP AND RIDGE INSTALLATION TO BE USED. AND, CLEARLY
 MARK ON PRODUCT APPROVAL ATTACHMENT METHOD. SEC.
 R905.3.7.1 FBC-RESIDENTIAL.
  
 12- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  