Plan Review Notes
Plan Review Notes For Permit 22070090
Permit Number 22070090
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-07-07 13:13:48FIRE REVIEW COMMENTS:
  
 1. THE SUBMITTED PLAN SHEETS A1 (EXISTING) AND A2
 (PROPOSED) ARE BOTH THE PROPOSED PLAN (NO EXISTING
 SHEET IS IN THE SUBMITTED PLANS). WITH THE CREATION OF
 GLASS WALL PARTITIONS, IT MAY CREATE AN EXIT ACCESS
 CORRIDOR THAT WILL NEED TO COMPLY WITH NFPA 101,
 CHAPTER 8. PLEASE CLARIFY ON THE SUBMITTAL.
  
 2. WITH THE CREATION OF GLASS WALL PARTITIONS, A
 PROPERLY LICENSED SPRINKLER CONTRACTOR SHALL CONDUCT AN
 EVALUATION TO ENSURE CODE COMPLIANT COVERAGE IS
 MAINTAINED PER NFPA 13.
  
 3. ANY AND ALL WORK ON ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) WILL REQUIRE SEPARATE
 PERMITS AND SHOP DRAWINGS.
  
 4. RESUBMITTALS SHOULD BE INDICATED ON THE PLAN WITH
 CLOUDING OR RESPOND IN NARRATIVE FORM.
  
 5. ANOTHER REVIEW MAY GENERATE ADDITIONAL QUESTIONS
 AND/OR COMMENTS.
  