| 2022-08-23 12:10:24 | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 22070066 |
| | 8/23/22 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. A GAS REVIEW WAS SET UP |
| | BECAUSE THE REVISED PLAN SHOWS A NEW GAS FIRED TANKLESS |
| | WATER HEATER ON THE EXTERIOR OF THE HOUSE. |
| | |
| | 1) SHEET P-1: A GAS RISER DRAWING IS REQUIRED PER SEC. |
| | 107.3.5.3 WPB, AND CHAPTER 24 FBC RES. PLEASE PROVIDE |
| | THE FOLLOWING INFORMATION ON THE DRAWING: |
| | A) LOCATION OF METER AND TYPE OF GAS. |
| | B) DELIVERY PRESSURE AT THE METER. |
| | C) WATER HEATER BTU LOAD, OTHER GAS APPLIANCE LOADS, |
| | AND THE TOTAL LOAD. |
| | D) TYPES AND SIZES OF PIPING. |
| | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | G) LOCATIONS OF REGULATORS & SHUTOFF VALVES. |
| | H) OUTLET PRESSURES AT REGULATORS. |
| | I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| | K) PIPE SIZING TABLES. |
| | |
| | 2) P-1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW GAS |
| | WATER HEATER INDICATING THE MAKE AND MODEL AND BTU |
| | CAPACITY- SEC. G2448.1 FBC RES. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |