| 2022-12-15 16:07:20 | 3RD REVIEW FBC-2020 RES. FUEL GAS |
| | PERMIT- 22070048 |
| | 12/15/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | |
| | 1) 3RD REQUEST FOR RESPONSE TO COMMENT 1A COPIED BELOW. |
| | A) GAS RISER: SHOW THE SIZE OF THE MAIN METALLIC SUPPLY |
| | PIPE FROM THE METER TO THE 1ST TEE, AND THE SIZE OF THE |
| | BRANCH PIPE SUPPLYING THE MAIN HOUSE APPLIANCES. |
| | THE NEW RISER SHOWS A TOTAL OF 485,000 BTU FOR THE LOW |
| | PRESSURE SYSTEM. ASSUMING THE TOTAL DEVELOPED LENGTH OF |
| | THE SYSTEM DOES NOT EXCEED 20 FT. A MINIMUM 1-1/4 MAIN |
| | SUPPLY IS REQUIRED. |
| | |
| | G2412.3 (401.3) MODIFICATIONS TO EXISTING SYSTEMS. |
| | IN MODIFYING OR ADDING TO EXISTING PIPING SYSTEMS, |
| | SIZES SHALL BE MAINTAINED IN ACCORDANCE WITH THIS |
| | CHAPTER. |
| | G2412.4 (401.4) ADDITIONAL APPLIANCES. |
| | WHERE AN ADDITIONAL APPLIANCE IS TO BE SERVED, THE |
| | EXISTING PIPING SHALL BE CHECKED TO DETERMINE IF IT HAS |
| | ADEQUATE CAPACITY FOR ALL APPLIANCES SERVED. IF |
| | INADEQUATE, THE EXISTING SYSTEM SHALL BE ENLARGED AS |
| | REQUIRED OR SEPARATE PIPING OF ADEQUATE CAPACITY SHALL |
| | BE PROVIDED. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |