Plan Review Notes
Plan Review Notes For Permit 22070048
Permit Number 22070048
Review Stop G
Sequence Number 3
Notes
Date Text
2022-12-15 16:07:203RD REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 22070048
 12/15/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) 3RD REQUEST FOR RESPONSE TO COMMENT 1A COPIED BELOW.
 A) GAS RISER: SHOW THE SIZE OF THE MAIN METALLIC SUPPLY
 PIPE FROM THE METER TO THE 1ST TEE, AND THE SIZE OF THE
 BRANCH PIPE SUPPLYING THE MAIN HOUSE APPLIANCES.
 THE NEW RISER SHOWS A TOTAL OF 485,000 BTU FOR THE LOW
 PRESSURE SYSTEM. ASSUMING THE TOTAL DEVELOPED LENGTH OF
 THE SYSTEM DOES NOT EXCEED 20 FT. A MINIMUM 1-1/4 MAIN
 SUPPLY IS REQUIRED.
  
 G2412.3 (401.3) MODIFICATIONS TO EXISTING SYSTEMS.
 IN MODIFYING OR ADDING TO EXISTING PIPING SYSTEMS,
 SIZES SHALL BE MAINTAINED IN ACCORDANCE WITH THIS
 CHAPTER.
 G2412.4 (401.4) ADDITIONAL APPLIANCES.
 WHERE AN ADDITIONAL APPLIANCE IS TO BE SERVED, THE
 EXISTING PIPING SHALL BE CHECKED TO DETERMINE IF IT HAS
 ADEQUATE CAPACITY FOR ALL APPLIANCES SERVED. IF
 INADEQUATE, THE EXISTING SYSTEM SHALL BE ENLARGED AS
 REQUIRED OR SEPARATE PIPING OF ADEQUATE CAPACITY SHALL
 BE PROVIDED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  