Plan Review Notes
Plan Review Notes For Permit 22070048
Permit Number 22070048
Review Stop G
Sequence Number 2
Notes
Date Text
2022-07-14 14:48:581ST REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 22070048
 7/8/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER: BASED ON TABLES 402.4(21) FBC FUEL GAS
 THE 17 FT. RUN OF 3/4 -INCH PE IS ADEQUATELY SIZED
 HOWEVER A COMPLETE RISER THAT INCLUDES THE EXISTING GAS
 PIPING AND APPLIANCES HAS NOT BEEN NOT PROVIDED- SEE
 SECS. G2412.3 & G2412.4 COPIED BELOW.
 A) SHOW THE SIZE OF THE MAIN METALLIC SUPPLY PIPE FROM
 THE METER TO THE 1ST TEE, AND THE SIZE OF THE BRANCH
 PIPE SUPPLYING THE MAIN HOUSE APPLIANCES. COMPLETE THE
 RISER AS NOTED ABOVE.
 B) THE PRINTED NAME AND SIGNATURE OF THE CONTRACTOR OR
 QUALIFIER SHALL BE ON THE RISER DRAWING- SEC. 107.2.1
 WPB.
  
 G2412.3 (401.3) MODIFICATIONS TO EXISTING SYSTEMS.
 IN MODIFYING OR ADDING TO EXISTING PIPING SYSTEMS,
 SIZES SHALL BE MAINTAINED IN ACCORDANCE WITH THIS
 CHAPTER.
 G2412.4 (401.4) ADDITIONAL APPLIANCES.
 WHERE AN ADDITIONAL APPLIANCE IS TO BE SERVED, THE
 EXISTING PIPING SHALL BE CHECKED TO DETERMINE IF IT HAS
 ADEQUATE CAPACITY FOR ALL APPLIANCES SERVED. IF
 INADEQUATE, THE EXISTING SYSTEM SHALL BE ENLARGED AS
 REQUIRED OR SEPARATE PIPING OF ADEQUATE CAPACITY SHALL
 BE PROVIDED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  