| Plan Review Notes For Permit 22061698 |
| Permit Number |
22061698 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-09-06 08:02:10 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 1.) FBC B 107.2.1, PROVIDE THE SPECIFICATIONS FOR THE | | | FLOORING TO BE USED, ENGINEERED WOOD (OAK) FLOORING. | | | 2.) FBC B 107.2.1, PROVIDE THE CORRECT TEST RESULTS FOR | | | THE UNDERLAYMENT THAT WILL BE USED WITH THE CORRECT | | | FLOORING. CLARIFY IF IT'S TILE OR ENGINEERED WOOD. | | | 3.) FBC B 107.2.1, INDICATE ON PLAN IF THE TUBS/SHOWER | | | WALLS ARE FIRE RATED WALLS (TENANT/CORRIDOR SEPARATION | | | WALLS). FOR THOSE WALLS, BE CLEAR ON PLANS THAT THE | | | FIRE RATING AND MOISTURE RESISTANCE WILL BE MAINTAINED. | | | TYPICALLY THIS IS ACHIEVED BY INSTALLING A LAYER OF | | | DRYWALL TO MEET THE FIRE RATING FOLLOWED BY ANOTHER | | | LAYER OF CEMENT BOARD FOR THE TILE. |
|