Text |
| 2022-08-02 16:09:07 | ROOFING PLAN REVIEW |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2017 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | NOTICE: A ROOFING SUB-PERMIT REQUIRED. |
| | PERMITS - 105.1 REQUIRED. |
| | |
| | 1. PROVIDE PRODUCT APPROVALS FOR SECONDARY WATER |
| | BARRIER PER FBC R905.1.1. |
| | UNDERLAYMENT FOR ROOF SLOPES 2:12 AND GREATER SHALL |
| | CONFORM TO THE APPLICABLE STANDARDS? AND SHALL BE |
| | APPLIED AND ATTACHED IN ACCORDANCE WITH SECTION |
| | R905.1.1.1, R905.1.1.2 OR R905.1.1.3, AS APPLICABLE. |
| | |
| | |
| | 2. FOR NOA 18-0919.12 (FLAT ROOF), DESIGNER SHALL |
| | SELECT THE SYSTEM TO BE INSTALLED, (WOOD DECK, |
| | NON-INSULATED). REVIEW THE GENERAL LIMITATIONS 6 AND 7 |
| | ON PG. 67/67. . ENHANCHED FASTENER SPACING, PREPARED BY |
| | A DESIGN PROFESSIONAL, MAY BE REQUIRED. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |