| 2022-08-02 17:41:24 | ROOFING REVIEW: |
| | |
| | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| | |
| | A)FLAT ROOF NOA 22-0107.02 SUBMITTED: SELECTED ASSEMBLY |
| | ON PAGE 17 OF 18 DOESN'T MEET THE DESIGN PRESSURES FOR |
| | ALL ROOF ZONES. PROVIDE SIGNED AND SEALED RAS 117 |
| | CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER |
| | AREAS AS REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE |
| | OF NOA. NEED THE CALCULATIONS TO MEET THE DESIGN |
| | PRESSURES REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. |
| | |
| | B)ROOF TILE NOA 21-1215.06 SUBMITTED. CLEARLY MARK |
| | ADHESIVE PADDY SIZE TO BE USED AS REQUIRED BY CITY |
| | POLICY FOR ALL ROOFING PERMITS TO VERIFY COMPLIANCE |
| | WITH THE DESIGN PRESSURES OF SEC R301.2.1 |
| | FBC-RESIDENTIAL. |
| | |
| | C)ROOF TILE ADHESIVE SELECTED ON ROOF TILE NOA. |
| | |
| | 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | NOTE: PRODUCT APPROVAL LETTER WAS NOT SIGNED BY THE |
| | ARCHITECT REVIEWING THE PRODUCT APPROVALS. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |