Plan Review Notes
Plan Review Notes For Permit 22061666
Permit Number 22061666
Review Stop R
Sequence Number 3
Notes
Date Text
2022-09-26 15:51:511- PROVIDE PRODUCT APPROVAL FOR:
 A)ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE
 USED. FLORIDA PRODUCT APPROVAL FL17330-R4 IS
 INCOMPLETE. MISSING INSTALLATION INSTRUCTIONS. ALSO,
 NEED TO SPECIFY PADDY SIZE.
 B)ROOF TILE ADHESIVE LISTED IN ROOF TILE PRODUCT
 APPROVAL.
 C)ROOFING UNDERLAYMENT. SINGLE PLY ROOF SYSTEMS
 FL14318-R18 SUBMITTED IS NOT A ROOF TILE UNDERLAYMENT.
 THIS IS ROOFING ASSEMBLY FOR FLAT ROOFS.
 D)HIP & RIDGE METAL SUPPORT TO BE USED.
 2- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS. NOTE: ROOFING UNDERLAYMENT INFO ON PRODUCT
 APPROVAL SCHEDULE ON SHEET 3.1 IS INCORRECT. SINGLE PLY
 ROOF SYSTEMS FL14318-R18 SUBMITTED IS NOT A ROOF TILE
 UNDERLAYMENT. THIS IS ROOFING ASSEMBLY FOR FLAT ROOFS.