| 2022-09-26 15:13:14 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | (NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO |
| | INSTALLATION/INSPECTIONS TO AVOID CONFLICTS/DELAYS). |
| | 1- ROOF FRAMING PLAN: (A)PROVIDE SECTION DETAIL FOR NEW |
| | (2)1-3/4"X16" LVL BEAM SHOWING HOW THE SIMPSON HANGER |
| | HU314-2 IS INSTALLED AT EACH END OF BEAM. |
| | NOTE: BEAM IS SITTING ON TOP OF THE MASONRY WALL. |
| | (B)NEW (2)1-3/4"X16" LVL BEAM: SPECIFY CONNECTORS |
| | RECEIVING EXISTING ROOF TRUSSES AND CONNECTORS |
| | RECEIVING NEW TRUSSES. |
| | C) PROVIDE DETAIL/ SPECS FOR BEAM ML2 SHOWN ON THE |
| | FRONT AND REAR ADDITIONS. |
| | 2- REVISE ROOF SHEATHING NAILING SPECIFICATIONS TO |
| | COMPLY WITH NEW 2020 FBC-RESIDENTIAL SPECIFICATIONS. |
| | TABLE R803.2.3.1 FBC-RESIDENTIAL. |
| | 3- WALL SECTION S3/5.1: PROVIDE DETAIL OF NEW BEARING |
| | KNEE WALL OVER EXISTING ROOF STRUCTURE. SPECIFY ALL |
| | FRAMING MEMBERS AND CONNECTORS. |
| | 4- SPECIFY ROOF CROSS VENTILATION. SPECIFY VENT SIZE |
| | AND LOCATION. |
| | 5- PROVIDE DOOR AND WINDOW STRUCTURAL BUCK DETAI. SEC. |
| | R609.7.2.1 FBC-RESIDENTIAL. SPECIFY STRUCTURAL BUCK |
| | SIZE AND FASTENING. |
| | NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO |
| | THE DOOR/WINDOW FRAME. |
| | 6- SOFFIT CONSTRUCTION DETAIL ON WALL SECTIONS: |
| | ENGINEER TO SPECIFY TYPE OF METAL PLASTER BASE FOR |
| | CEILINGS SHOWING COMPLIANCE WITH TABLE 3 OF ASTM C1063. |
| | NOTE: ALSO, PROVIDE DETAIL/SPECIFICATIONS FOR CEILING |
| | CONSTRUCTION AT NEW MASTER LANAI. |
| | 7- SHEET 6.1: ENGINEER TO REVISE END ZONE DISTANCE. THE |
| | MINIMUM DIMENSION IS 4'-0" NOT 3'-0" AS REQUIRED BY |
| | NOTE "A" ON FIGURE R301.2(7) FBC-RESIDENTIAL. |
| | 8- TRUSS PACKAGE NEEDS TO BE APPROVED BY THE ENGINEER |
| | OF RECORD. AND, NEEDS TO BE HANDLED TO THE BUILDING |
| | INSPECTOR DURING THE FRAMING INSPECTION. |
| | 9- PROVIDE PRODUCT APPROVAL FOR: |
| | A)EXTERIOR DOORS. JELD-WEN FLORIDA PRODUCT APPROVAL |
| | FL16708-R13 IS INCOMPLETE. NEED INSTALLATION |
| | INSTRUCTIONS DRAWINGS. |
| | B)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE |
| | TO VERIFY PRESSURES. |
| | C)ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE |
| | USED. FLORIDA PRODUCT APPROVAL FL17330-R4 IS |
| | INCOMPLETE. MISSING INSTALLATION INSTRUCTIONS. ALSO, |
| | NEED TO SPECIFY PADDY SIZE. |
| | D)ROOF TILE ADHESIVE LISTED IN ROOF TILE PRODUCT |
| | APPROVAL. |
| | E)ROOFING UNDERLAYMENT. SINGLE PLY ROOF SYSTEMS |
| | FL14318-R18 SUBMITTED IS NOT A ROOF TILE UNDERLAYMENT. |
| | THIS IS ROOFING ASSEMBLY FOR FLAT ROOFS. |
| | F)HIP & RIDGE METAL SUPPORT TO BE USED. |
| | 10- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT |
| | APPROVALS. NOTE: ROOFING UNDERLAYMENT INFO ON PRODUCT |
| | APPROVAL SCHEDULE ON SHEET 3.1 IS INCORRECT. SINGLE PLY |
| | ROOF SYSTEMS FL14318-R18 SUBMITTED IS NOT A ROOF TILE |
| | UNDERLAYMENT. THIS IS ROOFING ASSEMBLY FOR FLAT ROOFS. |
| | REVISE SCHEDULE AS REQUIRED AND INCLUDE MISSING PRODUCT |
| | APPROVALS. |
| | 11- REVISE ENERGY CALCULATIONS SUBMITTED: |
| | A)NUMBER OF BEDROOMS ON PAGE 1 IS INCORRECT. |
| | B)CEILING R-VALUE ON PAGE 1 DOESN'T MATCH PLANS. |
| | C)DOORS ORIENTATION DOESN'T MATCH PLANS. |
| | D)REVISE WINDOWS INFORMATION ON PAGE 4. WINDOWS |
| | ORIENTATION, MATERIAL, AND OVERHANG SEPARATION TO MATCH |
| | PLANS. |
| | E)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| | (EPL) DISPLAY CARD. |
| | F)ENGINEER SPECIFIES 1/300 ATTIC VENT RATIO ON PAGE 4. |
| | PLANS DON'T SHOW THIS VENTILATION RATIO. ENGINEER TO |
| | PROVIDE DETAILS/SPECS SHOWING COMPLIANCE WITH 1/300 |
| | RATIO. SEC. R806.2 FBC-RESIDENTIAL. |