Plan Review Notes
Plan Review Notes For Permit 22061666
Permit Number 22061666
Review Stop B
Sequence Number 3
Notes
Date Text
2022-09-26 15:13:14BUILDING REVIEW APPROVED WITH PROVISO:
 (NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO
 INSTALLATION/INSPECTIONS TO AVOID CONFLICTS/DELAYS).
 1- ROOF FRAMING PLAN: (A)PROVIDE SECTION DETAIL FOR NEW
 (2)1-3/4"X16" LVL BEAM SHOWING HOW THE SIMPSON HANGER
 HU314-2 IS INSTALLED AT EACH END OF BEAM.
 NOTE: BEAM IS SITTING ON TOP OF THE MASONRY WALL.
 (B)NEW (2)1-3/4"X16" LVL BEAM: SPECIFY CONNECTORS
 RECEIVING EXISTING ROOF TRUSSES AND CONNECTORS
 RECEIVING NEW TRUSSES.
 C) PROVIDE DETAIL/ SPECS FOR BEAM ML2 SHOWN ON THE
 FRONT AND REAR ADDITIONS.
 2- REVISE ROOF SHEATHING NAILING SPECIFICATIONS TO
 COMPLY WITH NEW 2020 FBC-RESIDENTIAL SPECIFICATIONS.
 TABLE R803.2.3.1 FBC-RESIDENTIAL.
 3- WALL SECTION S3/5.1: PROVIDE DETAIL OF NEW BEARING
 KNEE WALL OVER EXISTING ROOF STRUCTURE. SPECIFY ALL
 FRAMING MEMBERS AND CONNECTORS.
 4- SPECIFY ROOF CROSS VENTILATION. SPECIFY VENT SIZE
 AND LOCATION.
 5- PROVIDE DOOR AND WINDOW STRUCTURAL BUCK DETAI. SEC.
 R609.7.2.1 FBC-RESIDENTIAL. SPECIFY STRUCTURAL BUCK
 SIZE AND FASTENING.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR/WINDOW FRAME.
 6- SOFFIT CONSTRUCTION DETAIL ON WALL SECTIONS:
 ENGINEER TO SPECIFY TYPE OF METAL PLASTER BASE FOR
 CEILINGS SHOWING COMPLIANCE WITH TABLE 3 OF ASTM C1063.
 NOTE: ALSO, PROVIDE DETAIL/SPECIFICATIONS FOR CEILING
 CONSTRUCTION AT NEW MASTER LANAI.
 7- SHEET 6.1: ENGINEER TO REVISE END ZONE DISTANCE. THE
 MINIMUM DIMENSION IS 4'-0" NOT 3'-0" AS REQUIRED BY
 NOTE "A" ON FIGURE R301.2(7) FBC-RESIDENTIAL.
 8- TRUSS PACKAGE NEEDS TO BE APPROVED BY THE ENGINEER
 OF RECORD. AND, NEEDS TO BE HANDLED TO THE BUILDING
 INSPECTOR DURING THE FRAMING INSPECTION.
 9- PROVIDE PRODUCT APPROVAL FOR:
 A)EXTERIOR DOORS. JELD-WEN FLORIDA PRODUCT APPROVAL
 FL16708-R13 IS INCOMPLETE. NEED INSTALLATION
 INSTRUCTIONS DRAWINGS.
 B)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO VERIFY PRESSURES.
 C)ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE
 USED. FLORIDA PRODUCT APPROVAL FL17330-R4 IS
 INCOMPLETE. MISSING INSTALLATION INSTRUCTIONS. ALSO,
 NEED TO SPECIFY PADDY SIZE.
 D)ROOF TILE ADHESIVE LISTED IN ROOF TILE PRODUCT
 APPROVAL.
 E)ROOFING UNDERLAYMENT. SINGLE PLY ROOF SYSTEMS
 FL14318-R18 SUBMITTED IS NOT A ROOF TILE UNDERLAYMENT.
 THIS IS ROOFING ASSEMBLY FOR FLAT ROOFS.
 F)HIP & RIDGE METAL SUPPORT TO BE USED.
 10- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS. NOTE: ROOFING UNDERLAYMENT INFO ON PRODUCT
 APPROVAL SCHEDULE ON SHEET 3.1 IS INCORRECT. SINGLE PLY
 ROOF SYSTEMS FL14318-R18 SUBMITTED IS NOT A ROOF TILE
 UNDERLAYMENT. THIS IS ROOFING ASSEMBLY FOR FLAT ROOFS.
 REVISE SCHEDULE AS REQUIRED AND INCLUDE MISSING PRODUCT
 APPROVALS.
 11- REVISE ENERGY CALCULATIONS SUBMITTED:
 A)NUMBER OF BEDROOMS ON PAGE 1 IS INCORRECT.
 B)CEILING R-VALUE ON PAGE 1 DOESN'T MATCH PLANS.
 C)DOORS ORIENTATION DOESN'T MATCH PLANS.
 D)REVISE WINDOWS INFORMATION ON PAGE 4. WINDOWS
 ORIENTATION, MATERIAL, AND OVERHANG SEPARATION TO MATCH
 PLANS.
 E)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD.
 F)ENGINEER SPECIFIES 1/300 ATTIC VENT RATIO ON PAGE 4.
 PLANS DON'T SHOW THIS VENTILATION RATIO. ENGINEER TO
 PROVIDE DETAILS/SPECS SHOWING COMPLIANCE WITH 1/300
 RATIO. SEC. R806.2 FBC-RESIDENTIAL.