| 2022-09-21 17:04:24 | ROOFING REVIEW: |
| | |
| | 1- PRODUCT APPROVALS |
| | PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 |
| | FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| | |
| | ORIGINAL COMMENT: |
| | A)ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE |
| | USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS |
| | TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC |
| | R301.2.1 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | FLORIDA PRODUCT APPROVAL FL17330-R4 IS INCOMPLETE. |
| | MISSING INSTALLATION INSTRUCTIONS. ALSO, NEED TO |
| | SPECIFY PADDY SIZE. |
| | |
| | ORIGINAL COMMENT: |
| | B)ROOF TILE ADHESIVE LISTED IN ROOF TILE PRODUCT |
| | APPROVAL. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | C)ROOFING UNDERLAYMENT SPECIFIED ON PLANS. |
| | |
| | RESPONSE: |
| | SINGLE PLY ROOF SYSTEMS FL14318-R18 SUBMITTED IS NOT A |
| | ROOF TILE UNDERLAYMENT. THIS IS ROOFING ASSEMBLY FOR |
| | FLAT ROOFS. |
| | |
| | ORIGINAL COMMENT: |
| | D)HIP & RIDGE METAL SUPPORT TO BE USED. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | NOTE: ROOFING UNDERLAYMENT INFO ON PRODUCT APPROVAL |
| | SCHEDULE ON SHEET 3.1 IS INCORRECT. SINGLE PLY ROOF |
| | SYSTEMS FL14318-R18 SUBMITTED IS NOT A ROOF TILE |
| | UNDERLAYMENT. THIS IS ROOFING ASSEMBLY FOR FLAT ROOFS. |
| | REVISE AS REQUIRED AND INCLUDE MISSING PRODUCT |
| | APPROVALS. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |