Plan Review Notes
Plan Review Notes For Permit 22061666
Permit Number 22061666
Review Stop B
Sequence Number 1
Notes
Date Text
2022-08-10 19:05:41RESIDENTIAL (R3)ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22061666
  
 NOTE:
 ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1- UNABLE TO PERFORM REVIEW. MISSING
 STRUCTURAL/ARCHITECTURAL DRAWINGS FOR CONSTRUCTION OF
 PROPOSED ADDITION/ALTERATION. SEC. 107.5.5.2 CITY
 AMENDMENTS. SEC. R301.1 FBC-RESIDENTIAL.
  
 2- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)EXTERIOR DOORS AS SHOWN ON PLANS.
 B)WINDOWS AS SHOWN ON PLANS.
 C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO VERIFY PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL).
 D)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 E)ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE
 USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC
 R301.2.1 FBC-RESIDENTIAL.
 F)ROOF TILE ADHESIVE ( IF USED) LISTED IN ROOF TILE
 PRODUCT APPROVAL.
 G)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
 H)HIP & RIDGE METAL SUPPORT TO BE USED.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 4- ENERGY CALCULATIONS SUBMITTED:
 A)THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF FORM
 THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE, AS
 PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO
 RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION AS REQUIRED BY SECTION R101.5.1.1.2
 FBC-RESIDENTIAL.
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE
 AND JURISDICTION NUMBER (THIS IS JURISDICTION 604700).
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 C)NUMBER OF BEDROOMS ON PAGE 1 IS INCORRECT. SEE PLANS
 AND REVISE AS REQUIRED. SECTION R101.5.1.1.2
 FBC-RESIDENTIAL.
  
 D)FLOOR TYPE SPECIFIED ON PAGE 1 IS INCORRECT. THIS IS
 A SLAB ON GRADE. WHAT IS "BG FLOOR, HEAVY DAMP SOIL, ON
 GR"?. REVISE AS REQUIRED.
 SECTION R101.5.1.1.2 FBC-RESIDENTIAL.
  
 E)WALL TYPE ON PAGE 1 IS INCORRECT. THERE IS NOT 2"X4"
 WOOD. SEE PLANS AND REVISE AS REQUIRED. SECTION
 R101.5.1.1.2 FBC-RESIDENTIAL.
  
 F)CEILING TYPE INFORMATION ON PAGE 1 IS NOT CLEAR.
 CLARIFY WHY ENTERING TILE, SLATE, CONC.?. THIS IS NOT A
 CEILING TYPE. ALSO, NEED TO SPECIFY IF THE CEILING IS
 VENTED OR NOT. THIS NEEDS TO BE COORDINATED WITH THE
 INFORMATION SHOWN ON PLANS. REVISE AS REQUIRED. SECTION
 R101.5.1.1.2 FBC-RESIDENTIAL.
 NOTE: ARCHITECTURAL PLANS WERE NOT SUBMITTED FOR
 REVIEW. THIS INFORMATION WILL BE REVIEWED WHEN PLANS
 ARE SUBMITTED.
  
 G)HOT WATER INFORMATION ON PAGE 1 IS INCORRECT.
 ACCORDING TO PLANS, THE HOT WATER HEATER IS GAS NOT
 ELECTRIC. REVISE AS REQUIRED. SECTION R101.5.1.1.2
 FBC-RESIDENTIAL.
  
 H)SPACES INFORMATION ON PAGE 2 IS INCORRECT. THERE IS A
 KITCHEN IN THIS HOUSE. AND, NUMBER OF PEOPLE IS
 TYPICALLY SHOWN NEXT TO THE EACH BEDROOM. REVISE AS
 REQUIRED. SECTION R101.5.1.1.2 FBC-RESIDENTIAL.
  
 I)TYPE OF ROOF ON PAGE 2 IS INCORRECT. THIS HOUSE IS
 HIP ROOF NOT GABLE. REVISE AS REQUIRED. SECTION
 R101.5.1.1.2 FBC-RESIDENTIAL.
  
 J)DOORS INFORMATION ON PAGE 4 CAN NOT BE REVIEWED AT
 THIS TIME. ARCHITECTURAL PLANS AND PRODUCT APPROVALS
 WERE NOT SUBMITTED FOR REVIEW. THIS INFORMATION WILL BE
 REVIEWED WHEN PLANS ARE SUBMITTED.
 NOTE: KEEP IN MIND THAT DOORS WITH GLAZING NEED TO BE
 ENTERED IN THE GLAZING SECTION NOT IN DOORS.
  
 K)WINDOWS INFORMATION ON PAGE 4 CAN NOT BE REVIEWED AT
 THIS TIME. ARCHITECTURAL PLANS AND PRODUCT APPROVALS
 WERE NOT SUBMITTED FOR REVIEW. THIS INFORMATION WILL BE
 REVIEWED WHEN PLANS ARE SUBMITTED: WINDOWS AREA, AND
 OVERHANG DEPTH AND SEPARATION.
  
 L)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,