| 2022-08-01 14:12:03 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | FROM PREVIOUS LIST: | | | | | | 2. THIS BUILDING HAS A 7" SLAB, SOUND TEST FOR AN 8" | | | SLAB WAS SUBMITTED. THE STC/IIC NEEDS TO BE TESTED WITH | | | A 7" OR THINNER SLAB, SEE COMMENT #3. | | | | | | 3. SEE PREVIOUS LIST FOR CODE REFERENCES | | | | | | PROVIDE THE FOLLOWING TEST REPORTS FOR THE PROPOSED | | | UNDERLAYMENT STC, IIC, FLAME SPREAD. PROFLEX MAXXIM 90 | | | IS PROPOSED, WE DO NOT HAVE THOSE TEST REPORTS ON FILE. | | | EITHER SELECT A PRODUCT FOR WHICH WE HAVE TEST REPORTS | | | ON FILE, OR PROVIDE THE FOLLOWING: | | | | | | A, B. STC/IIC - RESPONSE LETTER STATES THAT WAS ALREADY | | | SUBMITTED. THAT TEST REPORT WAS DONE WITH AN 8" SLAB. | | | THIS UNIT HAS A 7" SLAB. | | | | | | C. FLAME SPREAD - 2ND REVIEW, TEST REPORT IS FOR | | | SUPERSIM 90, NOT MAXXIM 90. | | | | | | IF YOU WOULD LIKE TO CHANGE THE PRODUCT PROPOSED FROM | | | PROFLEX MAXXIM 90 TO SUPERSIM 90, REVISE PLAN. TEST | | | REPORTS THAT WE HAVE ON FILE WILL BE UPLOADED FOR YOU. |
|