Plan Review Notes
Plan Review Notes For Permit 22061647
Permit Number 22061647
Review Stop B
Sequence Number 2
Notes
Date Text
2022-09-19 10:57:37GENERATOR CONCRETE PAD ENGINEERING SECOND BUILDING
 AUDIT.
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22061647
 3105 AUSTRALIAN CT
  
 GENERATOR CONCRETE PAD ENGINEERING SHEET E1:
 ORIGINAL COMMENT:
 A)DESIGN CRITERIA NOTES SPECIFY "GENERATOR TO BE
 FASTENED WITH (3)5"X1/4" NON-CORROSIVE ZINC-PLATED
 BOLTS W/1 1/8" WASHERS OR EQ".
 ENGINEER OF RECORD DOESN'T PROVIDE DETAIL SHOWING
 LOCATION OF THE BOLTS ON THE CONCRETE SLAB.
 SPECIFIED ANCHOR NEEDS TO BE SPECIFIC. SPECIFYING "OR
 EQ." TO BE USED AS A SUBSTITUTE FOR THIS SPECIFIC
 ANCHOR IS NOT ALLOWED BY SEC. 107.2.1 CITY AMENDMENTS.
 REVISE DESIGN CRITERIA NOTES AND CONCRETE SLAB DETAIL
 AS REQUIRED. CITY AMENDMENTS AND SEC. R301.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 DRAWING E1 WAS REVISED WITH NEW DRAWING SHEET 1. DESIGN
 CRITERIA NOTE #4 CALLS FOR A STAND TO BE FASTENED W/(3)
 4"X5/8" NON-CORROSIVE BOLTS. DRAWINGS AND
 SPECIFICATIONS FOR THE PROPOSED STAND WERE NOT
 SUBMITTED. ALSO, PROVIDE COMPLETE DRAWINGS AND
 SPECIFICATIONS SHOWING HOW THE PROPOSED STAND IS
 FASTENED WITH 3 BOLTS AS SPECIFIED ON DESIGN NOTE #4.
 ALSO, SPECIFY FASTENING OF THE GENERATOR TO THE
 PROPOSED STAND.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.1
 FBC-RESIDENTIAL.
  
  
 ORIGINAL COMMENT:
 B) THE WEIGHT AND DIMENSIONS OF THE GENERATOR SPECIFIED
 ON THE DESIGN CALCULATIONS DOESN'T MATCH THE
 INFORMATION OF THE GENERATOR SPECS SUBMITTED. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. THE INFORMATION SUBMITTED DOESN'T MATCH
 THE INFORMATION OF THE GENERATOR SPECS SUBMITTED.
 INFORMATION PROVIDED IS FOR THE 24KW GENERATOR NOT FOR
 THE 22KW GENERATOR. REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS AND SEC. R301.1
 FBC-RESIDENTIAL.
  
  
 ORIGINAL COMMENT:
 2- DIGITAL SIGNATURE
 1- ENGINEER DRAWING HAVE A COPY OF A DIGITAL SIGNATURE
 THAT CAN NOT BE VERIFIED. ALL DRAWINGS/DOCUMENTS NEED
 TO HAVE VERIFIABLE ORIGINAL DIGITAL SEAL/SIGNATURE AS
 REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING
 DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
 NEED TO SUBMIT DRAWINGS ELECTRONICALLY WITH VERIFIABLE
 DIGITAL SIGNATURE.
  
 RESPONSE:
 REPEAT COMMENT.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 AUDIT COMMENT WITH A DESCRIPTION OF WHERE AND HOW THE
 COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE AUDIT
 PROCESS. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]