Plan Review Notes
Plan Review Notes For Permit 22061647
Permit Number 22061647
Review Stop B
Sequence Number 1
Notes
Date Text
2022-08-19 16:46:45GENERATOR CONCRETE PAD ENGINEERING BUILDING AUDIT.
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22061647
 3105 AUSTRALIAN CT
  
 GENERATOR CONCRETE PAD ENGINEERING SHEET E1:
 A) DESIGN CRITERIA NOTES SPECIFY "GENERATOR TO BE
 FASTENED WITH (3)5"X1/4" NON-CORROSIVE ZINC-PLATED
 BOLTS W/1 1/8" WASHERS OR EQ".
 ENGINEER OF RECORD DOESN'T PROVIDE DETAIL SHOWING
 LOCATION OF THE BOLTS ON THE CONCRETE SLAB.
 SPECIFIED ANCHOR NEEDS TO BE SPECIFIC. SPECIFYING "OR
 EQ." TO BE USED AS A SUBSTITUTE FOR THIS SPECIFIC
 ANCHOR IS NOT ALLOWED BY SEC. 107.2.1 CITY AMENDMENTS.
 REVISE DESIGN CRITERIA NOTES AND CONCRETE SLAB DETAIL
 AS REQUIRED. CITY AMENDMENTS AND SEC. R301.1
 FBC-RESIDENTIAL.
  
 B)THE WEIGHT AND DIMENSIONS OF THE GENERATOR SPECIFIED
 ON THE DESIGN CALCULATIONS DOESN'T MATCH THE
 INFORMATION OF THE GENERATOR SPECS SUBMITTED. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS AND
 SEC. R301.1 FBC-RESIDENTIAL.
  
 2- DIGITAL SIGNATURE
 1- ENGINEER DRAWING HAVE A COPY OF A DIGITAL SIGNATURE
 THAT CAN NOT BE VERIFIED. ALL DRAWINGS/DOCUMENTS NEED
 TO HAVE VERIFIABLE ORIGINAL DIGITAL SEAL/SIGNATURE AS
 REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING
 DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
 NEED TO SUBMIT DRAWINGS ELECTRONICALLY WITH VERIFIABLE
 DIGITAL SIGNATURE.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 AUDIT COMMENT WITH A DESCRIPTION OF WHERE AND HOW THE
 COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE AUDIT
 PROCESS. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,