| 2022-10-21 09:59:41 | 2ND PLUMBING REVIEW |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. DONE |
| | |
| | 2. DONE |
| | |
| | 3. DONE |
| | |
| | 4. NOT ADDRESSED - SHOW COMPLIANCE WITH 2020 FPC - |
| | 607.1.1 (HOT WATER DELIVERY) 2020 FPC - 607.1.1 |
| | TEMPERATURE LIMITING MEANS - ALL HOT/TEMPERED WATER |
| | MUST BE LIMITED BY A MIXING DEVICE. THE THERMOSTAT |
| | CONTROL ON THE WATER HEATER CANNOT BE THE LIMITING |
| | DEVICE FOR HOT/TEMPERED WATER DELIVERY. PLEASE PROVIDE |
| | A DETAIL FOR A LIMITING DEVICE FOR THE PURPOSE OF HOT |
| | WATER DELIVERY. THIS WOULD BE IN ADDITION TO THE |
| | REQUIREMENTS FOR TEMPERED WATER SUPPLIED FOR PUBLIC |
| | HANDWASHING 607.1.2/419.5. ALSO, THE DEVICE SHALL MEET |
| | THE ASSE 1017 STANDARD AND BE INSTALLED AT THE HOT |
| | WATER SOURCE PER 613.1. |
| | |
| | 5. DONE |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |