| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMENDS 107.2.1 - THE "EXISTING/DEMO" PLAN |
| | AND THE PROPOSED PLAN APPEAR TO BE IDENTICAL. PLEASE |
| | CLARIFY IF NO MODIFICATIONS ARE TO TAKE PLACE OR |
| | SUBMIIT AN ACCURATE "EXISTING" FLOOR PLAN. |
| | |
| | 2. 2017 WPB AMENDS 107.3.5 - PLEASE INDICATE THE |
| | OCCUPANT LOAD AND CLASSIFICATION OF SPACE FOR |
| | COMPLIANCE WITH SECTION 2020 FPC 403. |
| | |
| | 3. PAGE P201 - NOTE #5 INDICATES RUNNING THE CONDENSATE |
| | FOR AN AC "TO THE NEAREST DRAIN". CONDENSATE FROM AC'S |
| | ARE PROHIBITED FROM DISCHARGING INTO THE SANITARY PER |
| | WPB ORD. SEC. 90 - 126. |
| | |
| | 4. SHOW COMPLIANCE WITH 2020 FPC - 607.1.1 (HOT WATER |
| | DELIVERY) |
| | |
| | 5. SHOW COMPLIANCE WITH 2020 FPC 607.1.2/419.5 |
| | (TEMPERED WATER DELIVERY) |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |