Plan Review Notes
Plan Review Notes For Permit 22061636
Permit Number 22061636
Review Stop M
Sequence Number 1
Notes
Date Text
2022-07-27 06:50:561ST REVIEW FMC
 PERMIT: 22061636
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A MASTER PLAN SHOWING THE LOCATION OF THIS
 TENANT SPACE. IT APPEARS THIS IS A 2 STORY BUILDING.
 WHICH FLOOR IS THIS TENANT LOCATED? FBC 107.2.1
  
 2) PROVIDE A NOTE ON THE MECHANICAL DRAWING SPECIFYING
 THAT THE AREA ABOVE THE CEILING IS A RETURN AIR PLENUM
 AND MUST MEET FMC 602
  
 3) PROVIDE RETURN AIR PATH FOR ROOM 116. FMC 601.5
  
 4) SHEET M201: PROVIDE DUCT SIZE SUPPLYING THE 48 INCH
 2 SLOT GRILLE IN THE RETAIL AREA. FBC 107.2.1
  
 5) PROVIDE THE ENERGY CALCULATIONS FOR THIS TENANT
 SPACE. FEC C402
  
 6) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THIS TENANT SPACE. FEC C403.2.1
  
 7) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THIS TENANT
 SPACE. FMC 403.3.1.1 AND TABLE 403.3.1.1
  
 8) PROVIDE THE REQUIRED EXHAUST FOR THE DRESSING ROOMS.
 FMC TABLE 403.3.1.1
  
 9) PROVIDE DETAILS OF THE REFRIGERATION LINES RUNNING
 FROM DS 1 TO THE CU 1 ON THE ROOF. ALSO PROVIDE A ROOF
 DETAIL SHOWING THE LOCATION OF CU 1 AND THE MCU ON THE
 ROOF. FBC 107.2.1
  
 10) IDENTIFY THE DRY COOLER ON THE MECHANICAL DRAWING
 AND PROVIDE DETAILS OF THE OUTDOOR AIR AND RETURN AIR
 FOR THIS SYSTEM. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  