| Plan Review Notes For Permit 22061636 |
| Permit Number |
22061636 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-07-06 12:04:16 | FIRE REVIEW COMMENTS: | | | PROVIDE THE DISTANCE IN THE REAR CORRIDOR IN FRONT OF | | | THE RESTROOMS (119/120) TO ENSURE IT DOES NOT EXCEED | | | DEAD END CORRIDOR LIMITS PER NFPA 101, 38.2.5 | | | PROVIDE DETAIL OF THE DOOR HARDWARE/LOCKING | | | ARRANGEMENTS FOR COMPLIANCE WITH NFPA 101M 7.2.1.5 | | | PROVIDE PRODUCT INFORMATION FOR THE RESILIENT FLOORING | | | FOR THE PRODUCT FIRE PERFORMANCE TO INCLUDE THE | | | CRITICAL RADIANT FLUX PER NFPA 101, 10.2.7 | | | C. WALKER | | | 561-804-4762 | | | [email protected] | | | | | | | | | |
|