2022-07-06 12:04:16FIRE REVIEW COMMENTS:
 PROVIDE THE DISTANCE IN THE REAR CORRIDOR IN FRONT OF
 THE RESTROOMS (119/120) TO ENSURE IT DOES NOT EXCEED
 DEAD END CORRIDOR LIMITS PER NFPA 101, 38.2.5
 PROVIDE DETAIL OF THE DOOR HARDWARE/LOCKING
 ARRANGEMENTS FOR COMPLIANCE WITH NFPA 101M 7.2.1.5
 PROVIDE PRODUCT INFORMATION FOR THE RESILIENT FLOORING
 FOR THE PRODUCT FIRE PERFORMANCE TO INCLUDE THE
 CRITICAL RADIANT FLUX PER NFPA 101, 10.2.7