| Plan Review Notes For Permit 22061610 |
| Permit Number |
22061610 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-07-26 10:42:47 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. FBC RESIDENTIAL 301, SEE PAGE 12 OF THE PRODUCT | | | APPROVAL, MOUNTING TYPE A REQUIRES A POURED CONCRETE | | | SUBSTRATE. EITHER PROPOSE A DIFFERENT MOUNTING TYPE OR | | | VERIFY FIELD CONDITION AND REVISE INSTALLATION | | | SCHEDULE. | | | | | | | | | | | | | | | |
|