| Plan Review Notes For Permit 22061584 |
| Permit Number |
22061584 |
|
| Review Stop |
Z |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2023-01-20 15:42:21 | 1.REPEAT COMMENT: THE SUBMITTED PLANS SHOW THE | | | UNDERGROUND ELECTRIC BEING SUPPLIED FROM AN FPL | | | POLE/TRANSFORMER THAT IS LOCATED ON PRIVATE PROPERTY ON | | | THE EAST SIDE OF S. DIXIE HIGHWAY. THE SURVEY NEEDS TO | | | SHOW THAT THE AREA WHERE YOU PLAN TO PULL POWER FROM | | | ACROSS PRIVATE PROPERTY IS LOCATED WITHIN A UTILITY | | | EASEMENT. IF NO EASEMENT IS PRESENT POWER WILL HAVE TO | | | BE DRAWN FROM AN ALTERNATIVE LOCATION. | | | | | | ***PLEASE NOTE, ZONING WILL NOT PASS THIS REVIEW | | | WITHOUT FURTHER CLARIFYING THIS CONDITION AND | | | IDENTIFYING CONNECTION IS MADE WITHIN AN EASEMENT OR | | | FROM A POLE THAT IS WITHIN THE ROW.*** | | | | | | 2. ON PAGE 003 WHERE THE PROPOSED POLE IS LOCATED, | | | PLEASE PROVIDE AT LEAST A 5 FT. CLEARANCE FROM THE | | | PROPOSED EXCAVATION WORK TO THE TREE PIT. (8 FT. FROM | | | TRUNK OF TREE TO PROPOSED EXCAVATION OR | | | TRENCH/HANDHOLE). WORK RISKS IMPACT TO ROOT SYSTEMS OF | | | TREE. | | | | | | CHRIS KIMMERLY, AICP | | | URBAN DESIGN PLANNER | | | 822.1426 [email protected] | | | |
|