| Plan Review Notes For Permit 22061584 |
| Permit Number |
22061584 |
|
| Review Stop |
Z |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-08-23 14:19:22 | 1. THE SUBMITTED PLANS SHOW THE UNDERGROUND ELECTRIC | | | BEING SUPPLIED FROM AN FPL POLE/TRANSFORMER THAT IS | | | LOCATED ON PRIVATE PROPERTY ON THE EAST SIDE OF S. | | | DIXIE HIGHWAY. THE SURVEY NEEDS TO SHOW THAT THE AREA | | | WHERE YOU PLAN TO PULL POWER FROM ACROSS PRIVATE | | | PROPERTY IS LOCATED WITHIN A UTILITY EASEMENT. IF NO | | | EASEMENT IS PRESENT, YOU WILL NEED TO PROVIDE OWNERS | | | CONSENT, OR GET THE POWER FROM AN ALTERNATIVE LOCATION. | | | | | | 2. PLEASE PROVIDE AN 8FT. BUFFER BETWEEN THE TRUNK OF | | | ANY TREES AND PALMS FROM ANY HANDHOLES, BOREPITS, AND | | | EXCAVATION WORK. RISKS IMPACT TO ROOT SYSTEM OF TREES. | | | | | | 3. POLE STEALTH DESIGN, HEIGHT, AND PROPOSED COLOR | | | MATCHES CITY STANDARDS. | | | | | | CHRIS KIMMERLY, AICP | | | URBAN DESIGN PLANNER | | | 822.1426 [email protected] | | | |
|